Yoshitake GD-55R-80 Water Pressure Reducing Valve

Yoshitake GD-55R-80 home boiler regulator and water pressure reducing valve for hot water heat exchangers. Features pressure balance structure and 80 kPa set pressure.

Yoshitake GD-55R-80 Water Pressure Reducing Valve

Yoshitake GD-55R-80 is a home boiler regulator used for hot water heat exchangers in cold areas. It features back-flow prevention, negative pressure operation, pressure balancing, an automatic recovery drain tap, and a built-in strainer.

Features

  1. The valve is pressure balance structure.
  2. Pipes can be installed either horizontally or vertically.
  3. Drain tap can operate by pushing and automatically recover to initial position.
  4. GD-91R can be easily installed by a cap nut, since the outlet connection is parallel screw.
  5. Valve and diaphragm are made of chlorine resistance synthetic rubber.

Yoshitake GD-55R-80 exterior view 1Yoshitake GD-55R-80 exterior view 2Yoshitake GD-55R-80 exterior view 3

Specifications

ApplicationCold and hot water
Inlet pressure100-750 kPa
Standard set pressure80±6 kPa
BodyBronze
DiaphragmSynthetic rubber
Valve / Check valveSynthetic rubber
StrainerScreen: Stainless steel
Frame: Synthetic resin
Strainer mesh60 mesh
Maximum temperature60°C
ConnectionGD-55R, 56R: JIS Rc 3/4
GD-91R: JIS G 3/4
Install directionHorizontal and vertical

Notes

  • Standard set pressure 65 kPa (JIS approved) is available for GD-55R-65 and GD-56R-65.
  • Standard set pressure 30-200 kPa is available for GD-55R and GD-56R.

Performance Chart

Open flow rate30 L/min or more
Closing pressure of back-flow prevent function3 kPa or less
Operate pressure of negative pressure operating functionOpen: -55 kPa or less
Close: 50 kPa or more

INFO

  • Open flow rate indicates the outlet flow rate when the inlet pressure is maintained at 100kPa and the outlet side is open.

Dimensions (mm) and Weights (kg)

Yoshitake GD-55R-80 dimensions 1Yoshitake GD-55R-80 dimensions 2Yoshitake GD-55R-80 dimensions 3

Characteristic Charts

Yoshitake GD-55R-80 pressure characteristic chartYoshitake GD-55R-80 flow characteristic chart

Maximum Pressure Limits

Water pressure reducing valveRelief valve for hot water makerMax. pressure of hot water heat exchanger
8095, 97100
8597100
120190200
150190200
170190200
(Unit: kPa)

Attention

Using the bold font valves to simple boiler (100 kPa) is illegal.

Precautions for Installation and Operation

  1. Clean up inside the pipe and remove foreign substances before installing the home boiler regulator.
  2. Water may leak from the negative pressure operating mechanism at the first time of water supplying. Please connect vinyl tube and conduct to drain.
  3. In the case of horizontal piping follow to the label and install the product sideways, in order to reduce remain water when draining.
  4. Please be sure to remove foreign substances and scales from inside of the piping before connecting the product to the piping.
  5. Install pipe at the relief valve outlet side and conduct to drain ditch. Also install the relief valve so as to check the operation visually.
  6. Relief valve will be opened by lifting the lever horizontally. Please check the operation 1-2 times a month.
  7. Styrofoam package can be used as heat insulating material to prevent freezing.

Piping Example

Yoshitake GD-55R-80 piping example

Structural Drawings

Yoshitake GD-55R-80 structural drawing 1Yoshitake GD-55R-80 structural drawing 2Yoshitake GD-55R-80 structural drawing 3