Armstrong OB-2000 series self-actuated externally piloted temperature regulators for steam. Available in 1/2"-6", up to 300 psig, featuring ductile iron construction.

Armstrong OB-2000 series is a high-performance externally piloted temperature regulator for large capacity applications such as heat exchangers, steam coils, steam dryers, plating tanks, and parts washers. It is self-actuated and requires no external energy source. Capillary units mount in any position and can be easily disconnected and interchanged, offering easy installation and maximum application flexibility. The series is available in sizes 1/2" through 6" with six temperature ranges and three capillary lengths.
Designed for standard steam applications.
Designed for large capacity and low-pressure steam applications.
The OB-2000PT is a diaphragm-operated externally piloted pressure/temperature combination regulator. It is used in applications where maximum pressure should be limited and the temperature of the heated medium is controlled using a single seated main valve.
| Component | Specification |
|---|---|
| Capillary Material | Copper Capillary Tube With 304 Stainless Steel Armor Shield |
| Capillary Temperature Ranges | 18-59°F (-8-15°C), 50-97°F (10-36°C), 86-144°F (30-62°C), 131-201°F (55-94°C), 176-260°F (80-127°C), 239-361°F (115-183°C) |
| Temperature Accuracy | ±2°F (±1°C) From Set Point |
| Capillary Lengths | 6-1/2 ft (2m) standard, 9-1/2 ft (3m), 16-1/2 ft (5m) |
| Bulb Material | Nickel Plated Copper Bulb |
| Bulb Connection | 3/4" (20 mm) NPT |
| Thermal Well Material | Brass (Standard) or 304 Stainless Steel |
| Thermal Well Connection | 1" (25 mm) NPT |
WARNING
Capillary can withstand a maximum of 36°F (20°C) above rated range. If desired set temperature is in temperature range overlap, select lower range.
| Component | Material |
|---|---|
| Main Valve Body | Ductile Iron ASTM A536 |
| Seat Type & Material | Single Seat Stainless Steel AISI 420 |
| Valve Material | Stainless Steel AISI 420 |
| Temperature Pilot Valve | Bronze ASTM B584 |
| Pressure Pilot (OB-2000PT) | Ductile Iron ASTM A536 |



Points to Remember When Installing:


DANGER
Equipment under pressure - Operating temperature > 100°C. Make sure temperature regulator is cold and all internal pressure has been relieved before handling or disassembly!
| Problem | Cause | Solution |
|---|---|---|
| Temperature regulator does not reach desired set temperature. | Improper adjustment. | Readjust according to Regulating Methods. |
| Faulty steam trap draining equipment. | Check trap and correct problem. | |
| Inadequate pressure to eliminate condensate. | Re-pipe system to gravity drain condensate. Clean Y strainer on inlet to valve. | |
| Main valve diaphragms are ruptured. | Replace main valve diaphragms. | |
| No transfer medium applied to thermal bulb. | Apply heat transfer paste to thermal bulb before installation in well. | |
| Temperature rises excessively. | Dirt or scale on main valve and main valve seat or flawed valve and seat. | Disassemble and clean valve and seat. In case of flawed valve and seat - replace. |
| Dirt or scale on pilot valve, pilot valve and seat. | Disassemble pilot and clean. Replace if damaged. | |
| Broken capillary system. | Replace capillary system. | |
| Bypass line leaks. | Repair bypass. | |
| Large variation between thermometer and temperature regulator setting. | Thermal bulb or thermometer are installed in wrong location. | Relocate thermal bulb in path of fluid so at least 3/4 of bulb is submerged in fluid and/or relocate thermometer closer to thermal bulb. |
| Inlet pressure too high. | Lower inlet pressure. On low load applications, the lower the inlet pressure, the more stable the control will be. |