Skip to content
Type 8652Industrial Ethernet8-SlotAirLINE Quick AluminiumD6/D10 BrassIP20

BURKERT 20031699 Type 8652 AirLINE 8-Slot Valve Island with Industrial Ethernet and Aluminium AirLINE Quick Plate

BURKERT 20031699 (Type 8652) is an 8-slot AirLINE valve island featuring Industrial Ethernet communication, AirLINE Quick aluminium adapter plate, brass D6/D10 push-in ports, and -1 to 10 bar operating pressure.

BURKERT 20031699 Type 8652 AirLINE 8-Slot Valve Island with Industrial Ethernet and Aluminium AirLINE Quick Plate

BURKERT 20031699 (Type 8652) is an 8-valve-slot AirLINE pneumatic valve island configured with an anodised aluminium AirLINE Quick adapter plate, engineered specifically for process automation installations. This pre-assembled configuration incorporates six active valve stations equipped with 2 x 3/2-way normally closed solenoid valves (circuit function C) alongside two blanking plates on positions 7 and 8. Process communication is executed over Industrial Ethernet protocols (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic) via dual RJ45 ports integrated into the ME43 fieldbus gateway module.

Operating across a pneumatic pressure span from -1.00 bar to 10.00 bar with an internal auxiliary pilot air supply (3.00 to 10.00 bar), the unit provides visual status reporting directly on an integrated backlit LC display. Diagnostics are shown as explicit text strings and standardized symbols, enabling direct fault localisation during commissioning and routine plant operations.

BURKERT 20031699 BURKERT Type 8652 AirLINE valve island overview

Configuration of Article 20031699 ​

Article 20031699 represents an engineered variant from the Burkert Type 8652 family with the following build specifications:

Specification ParameterValue
Article Number20031699
Product Type8652 AirLINE
Base VariantStandard, 8-bank AirLINE Quick AL
Total Valve Slots8 PCE
Valve Slot Position 12x 3/2-way CF-C (normally closed)
Valve Slot Position 22x 3/2-way CF-C (normally closed)
Valve Slot Position 32x 3/2-way CF-C (normally closed)
Valve Slot Position 42x 3/2-way CF-C (normally closed)
Valve Slot Position 52x 3/2-way CF-C (normally closed)
Valve Slot Position 62x 3/2-way CF-C (normally closed)
Valve Slot Position 7Blind plate
Valve Slot Position 8Blind plate
Supply Port Dimension & MaterialD10 push-in, Brass
Working Port Dimension & MaterialD6 push-in, Brass
Adapter Plate MaterialAnodised aluminium
Additional Air Supply ConnectionsLeft: Push-in D6 and D10; Right: Push-in D6 and D10
Intermediate Feed Quantity0 PCE (without intermediate module)
Auxiliary Pilot AirInternal supply (3 to 10 bar)
Digital Input Count0 (Electronic modules with DI not fitted)
Exhaust Check ValvesNot fitted in port 3 (R) or 5 (S)
Pneumatic HotSwapNot fitted in port 1 (P)
Degree of ProtectionIP20 (bare); IP65 in closed cabinet with AirLINE Quick

Technical Specifications ​

CharacteristicTechnical Specification
Valve Body MaterialPolyamide (PA)
Seal MaterialsNBR and PUR
Station Width11 mm per valve slice
Maximum WidthDependent on slot count (see dimensions section)
Operating MediumLubricated or oil-free dry compressed air, neutral gases
Air Quality StandardISO 8573-1:2010, Class 7.4.4 (5 µm pre-filtering recommended)
Nominal Air Flow Rate ($Q_{\text{Nn}}$)310 l/min (measured at +20 °C, 6 bar inlet, 1 bar pressure drop)
Pressure RangeVacuum to 10 bar (-1.00 bar to 10.00 bar)
Auxiliary Pilot Pressure3.00 bar to 10.00 bar
Nominal Operating Voltage24 V DC (±10% tolerance, max. residual ripple 1 $V_{\text{ss}}$)
Valve Power Consumption0.7 W nominal (drops to 0.175 W after internal power reduction)
Valve Nominal Current29 mA (drops to 10 mA after power reduction)
Electrical Protection ClassClass III per DIN EN 61140, VDE 0140
Operating ModeContinuous operation (100% duty cycle)
Switching TimesTested in accordance with ISO 12238 (15 ms to 25 ms)
Ambient Temperature-10 °C to +55 °C
Storage Temperature-20 °C to +60 °C

AirLINE Quick Adapter Interface ​

Article 20031699 includes the AirLINE Quick adapter plate constructed from anodised aluminium with nickel-plated brass push-in fittings. This mounting mechanism attaches the valve island directly to cutouts on the control cabinet floor or wall.

BURKERT 20031699 BURKERT Type 8652 AirLINE Quick adapter plate

Control Cabinet Layout Benefits

Mounting via the AirLINE Quick plate eliminates bulkhead pass-through fittings and interior pneumatic hose routings. Pneumatic lines connect directly on the exterior underside of the cabinet, reducing space requirements inside the enclosure and allowing smaller cabinet volumes.

Mechanical PropertyValue
Adapter Plate MaterialAnodised aluminium (optional 1.4301 stainless steel)
Pneumatic Fitting MaterialNickel-plated brass (optional 1.4401 stainless steel)
Supply & Exhaust PortsPush-in D10 mm (3/8")
Working PortsPush-in D6 mm (1/4")
Enclosure Ingress ProtectionIP65 achieved across cabinet interface

Valve Functions and Pilot Solenoids ​

Type 8652 uses Type 6534 pilot solenoid valves (utilizing Type 6164 pilot elements) mounted on 11 mm slices. In article 20031699, positions 1 through 6 feature double 3/2-way valves in normally closed configuration (Circuit Function C), providing two independent single-acting actuator controls per physical slot.

Circuit FunctionSymbolWorking DescriptionFlow Rate ($Q_{\text{Nn}}$)Opening / Closing Time
CF C (2x 3/2-way)2x 3/2-way NCTwo 3/2-way pilot valves, servo-assisted, normally closed, manual override270 l/min15 ms / 15 ms
CF D (2x 3/2-way)2x 3/2-way NOTwo 3/2-way pilot valves, servo-assisted, normally open, manual override310 l/min15 ms / 15 ms
CF H (5/2-way)5/2-way single coilSingle solenoid 5/2-way valve, servo-assisted, manual override290 l/min20 ms / 25 ms
CF Z (5/2-way impulse)5/2-way bistableImpulse valve with 2 coils, servo-assisted, manual override290 l/min20 ms / 25 ms
CF L (5/3-way locked)5/3-way mid-closedCenter position all ports locked, servo-assisted275 l/min15 ms / 15 ms
CF M (5/3-way pressurized)5/3-way mid-pressurizedCenter position ports 2 and 4 pressurized, servo-assisted300 l/min20 ms / 20 ms
CF N (5/3-way exhausted)5/3-way mid-exhaustedCenter position ports 2 and 4 exhausted, servo-assisted300 l/min20 ms / 20 ms

Replacement Valve Ordering Numbers ​

Valve DescriptionCircuit FunctionVoltageArticle No. (Spare Part Set)
Solenoid valve Type 65342x 3/2-way NC (CF C)24 V DC301374 (REF 296031)
Solenoid valve Type 65342x 3/2-way NO (CF D)24 V DC301375 (REF 296032)
Solenoid valve Type 65345/2-way (CF H)24 V DC301376 (REF 296033)
Solenoid valve Type 65345/2-way impulse (CF Z)24 V DC301377 (REF 296034)
Solenoid valve Type 65345/3-way locked (CF L)24 V DC301380 (REF 296036)
Solenoid valve Type 65345/3-way pressurized (CF M)24 V DC301379 (REF 296035)
Solenoid valve Type 65345/3-way exhausted (CF N)24 V DC301381 (REF 296039)
Single 3/2-way NC1x 3/2-way NC (CF C)24 V DC20102334 (REF 20088974)
Dummy blanking plate——335779 (REF 327614)

Electrical and Fieldbus Connections ​

Electrical supply for logic and communication is segregated from the pneumatic valve actuator supply to permit safety trip functionality.

Power Supply Segregation

Maintain separate 24 V DC feeds for electronic logic and pneumatic valve coils. The interface plate provides independent spring-loaded terminal strips for communication power and valve auxiliary supply.

5-Pin Communication and Display Power Terminal ​

Accommodates conductor cross-sections up to 1.5 mm²:

Terminal PinConductor ColourSignal Assignment
1Red+24 V DC
2WhiteCAN_H (büS connection)
3GreenShielding
4BlueCAN_L (büS connection)
5Black0 V DC (GND)

2-Pin Pneumatic Valve Supply Terminal ​

Terminal ClipConductor ColourSignal Assignment
1RedAUX +24 V DC
2Black0 V DC (GND)

Industrial Ethernet Dual RJ45 Interface (X1 and X2) ​

The integrated fieldbus module supports daisy-chain topologies through dual MDI/MDI-X RJ45 female ports:

Contact PinSignal AssignmentProtocol Support
Pin 1TX+PROFINET IO
Pin 2TX-EtherNet/IP
Pin 3RX+Modbus TCP
Pin 4Not connectedEtherCAT
Pin 5Not connectedCC-Link IE Field Basic
Pin 6RX-PROFINET S2 redundancy
Pin 7Not connected—
Pin 8Not connected—

Installation and Cabinet Dimensions ​

Installation inside an enclosure requires adherence to minimum front clearance distances to allow valve replacement or servicing.

BURKERT 20031699 BURKERT Type 8652 control cabinet installation minimum distances

Mechanical Dimensions for 4-, 8-, and 12-Slot Variants ​

Valve Island VariantDimension A (mm)Dimension B (mm)Fastening Screws CParameter mParameter n
4-fold66—4x M531
8-fold (Article 20031699)351118x M572
12-fold7715410x M5113

Standard DIN rail mounting is compliant with EN 50022 profiles (35 x 7.5 mm or 35 x 15 mm). When installed on the control cabinet floor via the AirLINE Quick plate, the unit uses M5 DIN 6912 socket head screws.

Product Architecture and Network Integration ​

BURKERT 20031699 BURKERT Type 8652 modular assembly and interface plate

The modular structure consists of an ME43 fieldbus gateway, an LC display module, pneumatic base modules with 11 mm valve slices, and supply/exhaust connection blocks. Communication between modules runs over the internal büS backbone.

BURKERT 20031699 BURKERT Type 8652 Industrial Ethernet network topology

In hierarchical systems, Type 8652 equipped with Industrial Ethernet acts as the fieldbus master node. Decentralized AirLINE 8652 islands fitted with büS interfaces can be networked as field slaves beneath the master node without supplementary network switches.

Type 8652 supports safety-oriented shutdown functions through hardware-isolated circuits:

  • Type 6534 SIA Valves: Valves feature dedicated external 2-pin screw terminals (0.14 to 1.5 mm²). Opening an external potential-free contact disconnects coil power individually, bypassing bus communication commands. Manual override is omitted on SIA valves.
  • Module-Based SIA Emergency Stop: Optional 12-pin spring-loaded terminal strip (0.14 to 1.5 mm², wire gauge AWG 26-16) enables collective interruption of valve groups. Required contact switching capacity is 1.5 A at 24 V DC.

Hazardous Area Approvals ​

When deployed under specific Bürkert order codes (PU17 or PX68), Type 8652 holds certifications for Zone 2 and Zone 22 hazardous environments:

Certification BodyIdentification CodeStandard Compliance
ATEXII 3G Ex ec IIC Gc
II 3D Ex tc IIIC Dc
BVS 20 ATEX E 031 U
IECExEx ec IIC Gc
Ex tc IIIC Dc
IECEx BVS 20.0024 U
cURus HazLoc (USA / Canada)Class I, Zone 2, AEx ec IIC Gc / Ex ec IIC Gc U
Class II, Zone 22, AEx tc IIIC Dc / Ex tc IIIC Dc U
Class I, Div 2, Groups A, B, C, D
Class II/III, Div 2, Groups F, G
UL 61010-1
CAN/CSA-C22.2 No. 61010-1
CCC (China)Ex ec IIC Gc / Ex tc IIIC DcGB/T 3836 series (SITIIAS)

Explosive Atmosphere Safety Precautions

Do not connect or disconnect electrical terminals when energized in explosive atmospheres. Pneumatic hot swapping of valves is strictly prohibited in hazardous environments unless the atmosphere has been verified to be non-explosive by authorized personnel. Enclosures housing the valve island must provide minimum IP54 ingress protection for Category 3G (gas) and minimum IP6X for Category 3D (dust).

Accessories and Software Ordering ​

Accessory DescriptionSpecification DetailArticle Number
5-Pin Spring Terminal StripCommunication and display power supply920180
2-Pin Spring Terminal StripPneumatic valve actuator power supply920442
Fieldbus Gateway Type ME43Industrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT)301799
Fieldbus Gateway Type ME43PROFIBUS DP interface301803
Fieldbus Gateway Type ME43CANopen / büS interface301802
Fieldbus Gateway Type ME43PROFINET S2 system redundancy interface20081296
USB büS Interface Set 1Type 8923 with stick, M12/micro-USB cables, terminating resistor, software772426
Bürkert Communicator SoftwareConfiguration and diagnostic toolType 8920
Fastening Screw SetM5 x 10 A2 DIN 6912 for AirLINE Quick cabinet floor mounting (10 pcs)308661
8-Fold AirLINE Quick Height AdapterFor mounting level adaptation754960
8-Fold Retaining PlateExternal cabinet mounting plate60005566
8-Fold AirLINE Quick Blank PlateCutout cover plate without intermediate feed754965