BURKERT 20081380 Type 8652 AirLINE valve island. 20-bank configuration with Industrial Ethernet, AirLINE Quick aluminium adapter, and IP20 protection for process automation.

BURKERT 20081380 Type 8652 AirLINE valve island is especially developed for process automation requirements. This specific model features a 20-bank configuration (20 PCE) with an Industrial Ethernet interface supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic. It is equipped with an aluminium AirLINE Quick adapter plate, D3/8 brass pressure ports, and D 1/4 brass working ports. The hardware is optimised for installation at the bottom of the control cabinet, and key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts to prevent unplanned actuation due to pressure peaks.

| Product properties | Description |
|---|---|
| Body Material | PA (polyamide) |
| Seal Material | NBR and PUR |
| Width per station | 11 mm |
| Number of valve slots | Max. 24 (Model 20081380 features 20 slots) |
| Pressure range | Vac to 10 bar (Nominal: -1 to 10 bar) |
| External supply air | 3 to 10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Operating voltage | 24 V DC (±10% tolerance) |
| Nominal power per valve | 0.7 W (0.175 W after power reduction) |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Ambient temperature | -10 °C to +55 °C |
| Degree of protection | IP20 (IP65 in closed control cabinets) |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:

The Type 8652 supports various standard circuit functions, including:

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
For the Industrial Ethernet variant (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic), the RJ45 interface (X1 and X2) pin assignment is as follows:

| Pin | Assignment |
|---|---|
| 1 | TX+ |
| 2 | TX- |
| 3 | RX+ |
| 4 | N.C. |
| 5 | N.C. |
| 6 | RX- |
| 7 | N.C. |
| 8 | N.C. |
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

Safety Instructions for Potentially Explosive Areas
When using Bürkert devices with codes PU17 or PX68 in potentially explosive areas, observe the following: