Skip to content
Pt100Class A4-20mAHARTIP65

Spirax Sarco EL2280 and EL2281 Temperature Sensors and Transmitters

Spirax Sarco EL2280 and EL2281 are high-precision Pt100 temperature sensors and transmitters featuring Class A RTD elements, 4-20mA HART communication, and a wide measurement range up to 800°C.

Spirax Sarco EL2280 and EL2281 Temperature Sensors and Transmitters

Spirax Sarco EL2280 and EL2281 are Pt100 platinum resistance temperature sensors designed for general industrial applications. Both models utilize a three-wire RTD sensing element compliant with EN 60751: Class A standards. The measurement range spans from -200°C to +800°C, with models intended for temperatures exceeding 300°C featuring an integrated heat radiator. These sensors provide reliable temperature monitoring for steam and other industrial fluid systems.

EL2280 Temperature Sensor

The EL2280 is a standard Pt100 RTD sensor. It provides a direct resistance output and is typically used with external controllers or indicators. It features a 1/2" NPT process connection and supports custom insertion depths ranging from 25mm to 1000mm.

Spirax Sarco EL2280 Temperature Sensor

EL2281 Temperature Transmitter

The EL2281 combines a Pt100 sensor with an integrated transmitter, providing a 4-20mA output with HART communication protocol. This allows for seamless integration with modern control systems and computers. The EL2281 includes a local LCD screen for real-time temperature display at the point of measurement. It shares the same connection and depth options as the EL2280.

Spirax Sarco el2280 Spirax Sarco EL2281 Temperature Transmitter with LCD

Thermowells

A standard 1/2" NPT threaded thermowell is provided. Additional process connections are available upon request, including various G/M/NPT threads, PN or ANSI flanges, and socket weld options. Thermowells are rated for a maximum operating pressure of 30 MPa and temperatures up to 800°C.

Spirax Sarco EL2280/EL2281 Threaded Thermowell

Technical Specifications

ParameterEL2280EL2281
Output SignalPt100 (EN 60751 Class A)4-20mA + HART
Power Supply-12-32V DC
Accuracy-±0.2%
Standard Range0 to 300°C0 to 300°C
Standard Insertion Depths25, 50, 75, 125, 225, 725mm25, 50, 75, 125, 225, 725mm
Protection RatingIP65IP65
Approx. Weight1.0 kg1.8 kg

HART Communication (EL2281 Only)

  • Communication Address: 0-15 (Default: 0)
  • Transmission Rate: 1200 bps
  • Transmission Distance: Max 1.5 km
  • Load Resistance: ≥ 250Ω for HART communication

Wiring

Spirax Sarco EL2280 Wiring Diagram

Installation Notes

  • Insertion Depth: For pipe installation, the suggested depth is 1/2 of the pipe diameter plus the height of the mounting boss.
  • Fluid Flow: The probe must not be installed in static (no-flow) zones within the pipeline.
  • Thermal Conductivity: If a thermowell is used, it is recommended to add thermal oil inside the well to improve response.
  • High Temperature: For steam systems, horizontal installation is recommended to protect electronics from high ambient temperatures.
  • Shielding: Use 3-core shielded cable for EL2280 and 2-core shielded cable for EL2281 to prevent signal interference.