TLV FL21 and FL32 QuickTrap balanced pressure thermostatic steam traps with fail-open design, universal flange, and built-in screens for steam mains and tracers.

TLV FL21 and FL32 QuickTrap are universal balanced pressure thermostatic steam traps featuring a "fail open" design. They are equipped with an inline replaceable and cleanable two-bolt universal flange and offer high air venting capability. These models are highly suitable for steam-using equipment that discharges condensate at temperatures slightly below saturation temperature, such as steam mains, tracer lines, dryers, and light process heaters.
The FL Series steam traps (connector body unit F46 or former connector unit F32 and steam trap units L21, L32 as well as L21-C, L32-C with built-in check valve) can be used without adjustment for medium capacity applications up to 2.1 or 3.2 MPaG (300 or 450 psig).
WARNING
To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range. Local regulations may restrict the use of this product to below the conditions quoted.
| No. | Description | Material | DIN* | ASTM/AISI* |
|---|---|---|---|---|
| 1 | Trap Body | Cast Stainl. Steel A351/A351M Gr.CF8 | 1.4312 | — |
| 2 | Connector Body | Cast Stainl. Steel A351/A351M Gr.CF8 | 1.4312 | — |
| 3 | Connecting Flange | Carbon Steel A105/A105M | 1.0460 | — |
| 4 | Snap Ring | Carbon Steel SWRH57 | 1.0535 | AISI1055 |
| 5 | Outer Connector Gasket | Graphite/Stainl. Stl. SUS304 | -/1.4301 | -/AISI304 |
| 6 | Inner Connector Gasket | Graphite/Stainl. Stl. SUS304 | -/1.4301 | -/AISI304 |
| 7 | Valve Seat | Stainless Steel SUS420F | 1.4028 | AISI420F |
| 8 | Trap Cover | Carbon Steel A105/A105M | 1.0460 | — |
| 9 | Cover Gasket | Graphite/Stainl. Stl. SUS316L | -/1.4404 | -/AISI316L |
| 10 | Screen inside/outside | Stainless Steel SUS304/430 | 1.4301/1.4016 | AISI304/430 |
| 11 | Screen Holder Gasket | Stainless Steel SUS316L | 1.4404 | AISI316L |
| 12 | Screen Holder | Cast Stainl. Steel A351/A351M Gr.CF8 | 1.4312 | — |
| 13 | X-element | Stainless Steel | — | — |
| 14 | X-element Guide | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 15 | Nameplate | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 16 | Spring Clip | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 17 | Cover Bolt | Alloy Steel A193/A193M Gr.B7 | 1.7225 | — |
| 18 | Trap Screen | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 19 | Connector Bolt | Alloy Steel SNB7 | 1.7225 | A193/A193M Gr.B7 |
| 20 | Connector Nameplate | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 21 | Flange | Cast Stainl. Steel A351/A351M Gr.CF8 / SUS304 | 1.4312 / 1.4301 | — / AISI304 |
| 22 | Steel Ball (Check Valve) | Stainless Steel SUS440C | 1.4125 | AISI440C |
*Equivalent materials.


| Size | L (mm) | W (mm) | W1 (mm) | Weight (kg) |
|---|---|---|---|---|
| 1/2" | 80 | 169 | 105 | 1.8 |
| 3/4" | 80 | 169 | 105 | 1.8 |
| 1" | 96 | 171 | 109 | 2.1 |
*BSP DIN 2999, other standards available.

| DN | L (mm) | W (mm) | W1 (mm) | φD (mm) | φC (mm) | h (mm) | Weight (kg) |
|---|---|---|---|---|---|---|---|
| 15 | 80 | 169 | 105 | 36 | 21.8 | 12 | 1.8 |
| 20 | 80 | 169 | 105 | 36 | 27.2 | 14 | 1.8 |
| 25 | 96 | 171 | 109 | 44 | 33.9 | 14 | 2.1 |
*ASME B16.11-2005, other standards available.
| DN | L (DIN 2501 PN25/40) | L (ASME 150RF) | L (ASME 300RF) | L (ASME 600RF) | W | W1 | Weight* (kg) |
|---|---|---|---|---|---|---|---|
| 15 | 150 | 150 | 150 | 180 | 169 | 105 | 3.4 |
| 20 | 150 | 150 | 150 | 180 | 169 | 105 | 4.3 |
| 25 | 160 | 160 | 160 | 190 | 169 | 105 | 4.8 |
*Weight is for DIN PN 25/40. Other standards available, but length and weight may vary.

There are no restrictions on the installation direction beyond the following conditions:
Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity. The inlet pipe should be as short and have as few bends as possible.
Horizontal Piping
Vertical Piping
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Faulty steam traps may result in losses due to steam leakage.

| Problem | Cause | Remedy |
|---|---|---|
| Condensate is not discharged or (blocked) discharge is poor | X-element is stuck to the valve seat | Clean |
| Screens and/or inlet/outlet channels are clogged with rust or scale | Clean | |
| Steam-locking | Study piping | |
| Trap operating pressure exceeds maximum specified operating pressure | Study inlet pressure | |
| Differential pressure is insufficient | Study inlet/outlet pressure | |
| Steam leakage or blow-off | Valve closure is obstructed by rust or scale, etc | Clean (inspect screens as well) |
| X-element and/or valve seat are worn or damaged | Replace X-element and/or valve seat | |
| X-element is broken | Replace X-element | |
| Severe vibration of trap | Reinforce trap piping supports | |
| Leakage from another location | Gaskets of connector, trap cover, screen holder or valve seat are worn or damaged | Repair gaskets |
| Cover bolts, connector flange bolts, screenholder, or valve seat are loose | Tighten to proper torque | |
| Inlet and discharge channels may be connected due to erosion | Replace trap (study trap capacity) | |
| Bypass valve is open or damaged | Repair or close valve |
Explore similar products in our catalog