TLV JH5RL-X / JH5RL-B / JH5RH-B Cast Steel Free Float Steam Trap

TLV JH5RL-X, JH5RL-B, and JH5RH-B cast steel free float steam traps with thermostatic air venting. Suitable for process equipment up to 80 barg and 425 °C.

TLV JH5RL-X / JH5RL-B / JH5RH-B Cast Steel Free Float Steam Trap

The TLV JH5RL-X, JH5RL-B, and JH5RH-B are reliable and durable cast steel free float steam traps designed for use on small to medium-size process equipment. The JH5RL-B and JH5RH-B models are also suitable for both superheated and high-pressure process equipment. They feature a self-modulating free float that provides continuous, smooth, low-velocity condensate discharge as process loads vary.

Key features include a precision-ground float, constant water seal, and three-point seating design that ensure a steam-tight seal, even under no-load conditions. With only one moving part—the free float—concentrated wear is prevented, providing a long maintenance-free service life. The JH5RL-X utilizes a thermostatic capsule (X-element) with a "fail open" feature that vents air automatically at close-to-steam temperature. The JH5RL-B and JH5RH-B utilize a thermostatic bimetal air vent valve for rapid startup. All models feature a built-in screen with a large surface area and allow easy, inline access to internal parts to simplify cleaning and reduce maintenance costs.

Specifications

ModelJH5RL-XJH5RL-BJH5RH-B
ConnectionScrewed, Socket Welded, FlangedScrewed, Socket Welded, FlangedSocket Welded, Flanged
Size1/2", 3/4", 1" / DN15-501/2", 3/4", 1" / DN15-50DN15-50
Orifice No.5, 10, 14, 22, 322, 5, 10, 14, 22, 32, 40, 4680
Max Operating Pressure (PMO)5, 10, 14, 22, 32 barg2, 5, 10, 14, 22, 32, 40, 46 barg80 barg
Max Differential Pressure (ΔPMX)5, 10, 14, 22, 32 bar2, 5, 10, 14, 22, 32, 40, 46 bar80 bar
Max Operating Temperature (TMO)240 °C400*/425 °C400*/425 °C
Type of Air VentX-element (6 °C subcooling)Bimetal (vents air up to approx. 100 °C)Bimetal (vents air up to approx. 100 °C)

WARNING

Maximum allowable pressure (PMA) and maximum allowable temperature (TMA) are PRESSURE SHELL DESIGN CONDITIONS, NOT OPERATING CONDITIONS. To avoid malfunctions, product damage, accidents or serious injury, install properly and DO NOT use this product outside the specification range.

Configuration

TLV JH5RL-X configuration and cross section

No.DescriptionMaterialNo.DescriptionMaterial
1BodyCast Steel A216 Gr.WCB14ConnectorStainless Steel SUS416
2CoverCarbon Steel A105 / Cast Steel A216 Gr.WCB15Connector GasketGraphite/Stainless Steel SUS316L
3FloatStainless Steel SUS316L16X-element GuideStainless Steel SUS304
4Orifice17X-elementStainless Steel
5Orifice GasketSoft Iron SUYP18Spring ClipStainless Steel SUS304
6Orifice PlugCast Stainless Steel A351 Gr.CF819Air Vent Valve SeatStainless Steel SUS420F
7Orifice Plug GasketSoft Iron SUYP20Snap RingStainless Steel SUS304
8Float CoverStainless Steel SUS30421Air Vent CaseCast Stainless Steel A351 Gr.CF8
9Screen inside/outsideStainless Steel SUS430/30422Bimetal PlateBimetal
10Socket/FlangeCarbon Steel A10523Air Vent ScreenStainless Steel SUS304
11Cover BoltAlloy Steel SNB7 / SNB1624Air Vent Valve Seat
12Cover NutCarbon Steel S45C25Air Vent Valve Plug
13Cover GasketGraphite/Stainless Steel SUS316L26Snap RingStainless Steel SUS304

Discharge Capacity

JH5RL-XTLV JH5RL-X discharge capacity chart

JH5RL-B / JH5RH-BTLV JH5RL-X TLV JH5RL-B and JH5RH-B discharge capacity chart

INFO

  1. Line numbers within the graph are orifice numbers.
  2. Differential pressure is the difference between the inlet and outlet pressure of the trap.
  3. Capacities are based on continuous discharge of condensate 6 °C below saturated steam temperature.
  4. Recommended safety factor: at least 1.5.

Proper Installation

WARNING

Installation, inspection, maintenance, repairs, disassembly, adjustment and valve opening/closing should be carried out only by trained maintenance personnel. Use the eyebolts for removing the cover only; DO NOT use the eyebolts for hoisting the product.

  1. Before installation, be sure to remove all protective seals.
  2. Before installing the trap, blow out the inlet piping to remove all dirt and oil.
  3. When hoisting the product, hang the rope around the inlet/outlet as close to the body as possible.
  4. Install the steam trap within the allowable inclination. Also make sure that the arrow mark on the body corresponds with the direction of flow.
  5. Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity. The inlet pipe should be as short and have as few bends as possible.
  6. Support the pipes properly within 800 mm (2.5 ft) on either side of the trap.
  7. Install a bypass valve to discharge condensate, and inlet and outlet valves to isolate the trap in the event of trap failure or when performing maintenance.
  8. Install a check valve at the trap outlet whenever more than one trap is connected to the condensate collection pipeline.
  9. The use of unions is recommended to facilitate connection and disconnection of screwed models.

Inspection and Maintenance

Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.

DANGER

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.

Parts Inspection Procedure

PartInspection Item
Body, Cover(s)Check inside for damage, dirt, grease, oil film, rust or scale
GasketsCheck for warping or damage
X-elementCheck for damage
Screen(s)Check for clogging, corrosion or damage
FloatCheck for deformation, damage, oil film or water inside
Air Vent Valve Seat, OrificeCheck for rust, scale, oil film, wear or damage

Troubleshooting

ProblemCauseRemedy
No condensate is discharged (blocked) or discharge is poorFloat is damaged or filled with condensateReplace the float
Orifice, screen or piping are clogged with rust or scaleClean
X-element is damagedReplace the X-element
The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differentialCompare specifications and actual operating conditions
Steam locking has occurredBlowdown through the bypass or close the trap inlet valve and allow the trap to cool
Steam is discharged or leaks from the trap outlet (blowing/steam leakage)Rust and scale have accumulated around the orifice or under the floatClean
Orifice is damagedReplace with new orifice
Float is deformed or coated with scaleClean or replace the float
Trap is installed above the maximum allowable inclination angleCorrect the installation
Vibration of trap occursLengthen inlet piping, then fasten it securely
The X-element is damaged, or clogged with rust or scaleClean or replace the X-element
Steam leaks from a place other than the trap outletDeterioration of or damage to gasketsReplace the gaskets
Leakage from eroded cavities of body or coverReplace the trap
Improper tightening torque for cover was usedTighten to the proper torque
Float is frequently damagedWater hammer occursExamine the piping for problems that can cause water hammer