TLV JH5SL-X, JH5SL-B, and JH5SH-B stainless steel free float steam traps with thermostatic air venting. Suitable for small to medium process equipment up to 6.5 MPaG and 425°C.

TLV JH5SL-X, JH5SL-B, and JH5SH-B are inline repairable stainless steel free float steam traps with thermostatic air venting. They are suitable for a wide range of applications with small-to-medium capacities and pressures up to 6.5 MPaG (JH5SH-B), such as heat exchangers, process heaters, and coils. The traps discharge condensate continuously and automatically, at a temperature slightly lower than saturation temperature.

DANGER
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.
WARNING
CAUTION
| Model | JH5SL-X | JH5SL-B | JH5SH-B |
|---|---|---|---|
| Connection | Screwed, Socket Welded, Flanged | Screwed, Socket Welded, Flanged | Socket Welded, Flanged |
| Size | 1/2", 3/4", 1" (DN 15, 20, 25, 40, 50) | 1/2", 3/4", 1" (DN 15, 20, 25, 40, 50) | DN 15, 20, 25, 40, 50 |
| Orifice No. | 5, 10, 22, 32 | 2, 5, 10, 22, 32, 40, 46 | 65 |
| Max. Operating Pressure (PMO) | 0.5, 1.0, 2.2, 3.2 MPaG | 0.2, 0.5, 1.0, 2.2, 3.2, 4.0, 4.6 MPaG | 6.5 MPaG |
| Max. Differential Pressure (ΔPMX) | 0.5, 1.0, 2.2, 3.2 MPa | 0.2, 0.5, 1.0, 2.2, 3.2, 4.0, 4.6 MPa | 6.5 MPa |
| Max. Operating Temperature (TMO) | 240°C | 400°C / 425°C | 400°C / 425°C |
| Type of Air Vent | X-element (6°C subcooling) | Bimetal (vents air up to approx. 100°C) | Bimetal (vents air up to approx. 100°C) |
Pressure Shell Design Conditions (Not Operating Conditions):

| No. | Description | Material | ASTM/AISI |
|---|---|---|---|
| 1 | Body | Cast Stainless Steel | A351 Gr.CF8 |
| 2 | Cover | Cast Stainless Steel | A351 Gr.CF8 |
| 3 | Float | Stainless Steel | AISI316L |
| 4 | Orifice | - | - |
| 5 | Orifice Gasket | Stainless Steel | AISI316L |
| 6 | Orifice Plug | Cast Stainless Steel | A351 Gr.CF8 |
| 7 | Orifice Plug Gasket | Stainless Steel | AISI316L |
| 8 | Cover Gasket | Graphite/Stainless Steel | -/AISI316L |
| 9 | Float Cover | Stainless Steel | AISI304 |
| 10 | Screen inside/outside | Stainless Steel | AISI430/304 |
| 11 | Spring Clip | Stainless Steel | AISI304 |
| 12 | X-element Guide | Stainless Steel | AISI304 |
| 13 | Air Vent Valve Seat | Stainless Steel | AISI420F |
| 14 | X-element | Stainless Steel | - |
| 15 | Connector | Stainless Steel | AISI416 |
| 16 | Connector Gasket | Graphite/Stainless Steel | -/AISI316L |
(Note: Parts list is abbreviated. Refer to the full manual for complete component details including bimetal specific parts).

| Size | L (mm) | H (mm) | H1 (mm) | W (mm) | Weight (kg) |
|---|---|---|---|---|---|
| 1/2" | 234 | 167 | 105 | 115 | 6.5 |
| 3/4" | 246 | 167 | 105 | 115 | 6.6 |
| 1" | 258 | 167 | 105 | 115 | 6.7 |




Notes:

| Requirement | Correct | Incorrect |
|---|---|---|
| Install a catchpot with the proper diameter. | Diameter is sufficient. | Diameter is too small. |
| Make sure the flow of condensate is not obstructed. | Flow is clear. | Diameter is too small and inlet protrudes into pipe. |
| To prevent rust and scale from flowing into the trap, connect the inlet pipe 25 - 50 mm (1 - 2 in) above the base of the T - pipe. | Connected above base. | Rust and scale flow into the trap with the condensate. |
| When installing on the blind end, make sure nothing obstructs the flow of condensate. | Flow is clear. | Condensate collects in the pipe. |
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
| Part | Inspection Item |
|---|---|
| Body, Cover(s) | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| X-element | Check for damage |
| Screen(s) | Check for clogging, corrosion or damage |
| Float | Check for deformation, damage, oil film or water inside |
| Air Vent Valve Seat, Orifice | Check for rust, scale, oil film, wear or damage |
| Part | JH5SL-X Torque (N·m) | Distance across Flats (mm) |
|---|---|---|
| Cover Bolt / Nut | 110 | 22 |
| Orifice | 140 | 17 |
| Orifice Plug | 180 | 38 |
| Air Vent Valve Seat | 35 | 19 |
| Drain Plug | 35 | 21 |
A visual inspection can be carried out to aid in determining the necessity for immediate maintenance or repair, if the trap is open to atmosphere.
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping are clogged with rust or scale | Clean | |
| X-element is damaged | Replace the X-element | |
| The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differential | Compare specifications and actual operating conditions | |
| Steam locking has occurred | Blowdown through the bypass or close the trap inlet valve and allow the trap to cool | |
| Steam is discharged or leaks from the trap outlet (blowing/steam leakage) | Rust and scale have accumulated around the orifice or under the float | Clean |
| Orifice is damaged | Replace with new orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely | |
| The X-element is damaged, or clogged with rust or scale | Clean or replace the X-element | |
| Steam leaks from a place other than the trap outlet | Deterioration of or damage to gaskets | Replace the gaskets |
| Leakage from eroded cavities of body or cover | Replace the trap | |
| Improper tightening torque for cover was used | Tighten to the proper torque | |
| Float is frequently damaged | Water hammer occurs | Examine the piping for problems that can cause water hammer |