Cast SteelInline RepairableBimetal Air Vent

TLV JH7.2R-B Free Float Steam Trap

TLV JH7.2R-B free float steam trap with thermostatic bimetal air venting. Designed for medium-to-large process equipment, featuring cast steel construction, 46 barg max pressure, and inline repairability.

TLV JH7.2R-B Free Float Steam Trap

TLV JH7.2R-B is a reliable and durable cast steel free float steam trap for use on medium-size and high-pressure process equipment. The inline repairable steam trap features a thermostatic bimetal air vent valve that automatically vents air for rapid startup. It is suitable for a wide range of applications with pressures up to 46 barg.

The self-modulating free float provides continuous, smooth, low-velocity condensate discharge as process loads vary, while a constant water seal design ensures a steam-tight seal even under low-load conditions. A built-in screen with a large surface area ensures extended trouble-free operation, and its inline access to internal parts simplifies cleaning and reduces maintenance costs.

Safety Considerations

DANGER

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.

WARNING

Install properly and DO NOT use this product outside the recommended operating pressure, temperature and other specification ranges. DO NOT use this product in excess of the maximum operating pressure differential. Such use could make discharge impossible. Wait until the internal pressure equals atmospheric pressure and the surface of the product has cooled to room temperature before disassembling or removing the product.

Configuration

TLV JH7.2R-B structural configuration and parts

No.DescriptionNo.DescriptionNo.Description
1Body13Cover Gasket25Snap Ring
2Cover14Connector26Drain Plug Gasket
3Float15Connector Gasket27Drain Plug
4Orifice16Snap Ring28Orifice Locknut
5Orifice Gasket17Air Vent Case29Outlet Cover Bolt
6Orifice Plug18Bimetal Plate30Outlet Cover Nut
7Plug/Cover Gasket19Air Vent Screen31Screen Holder Retainer
8Float Cover20Air Vent Valve Seat32Air Vent Guide Gasket
9Screen21Air Vent Valve Plug33Air Vent Guide
10Flange or Socket22Snap Ring34Eye Bolt
11Cover Bolt23Nameplate
12Cover Nut24Screen Holder

Specifications

TLV JH7.2R-B nameplate details

Pressure Shell Design Conditions (Not Operating Conditions):

  • Maximum Allowable Pressure (PMA): 46 barg
  • Maximum Allowable Temperature (TMA): 400 °C / 425 °C (with PN flange)
No.DescriptionMaterialDINASTM/AISI
1BodyCast Steel A216 Gr.WCB1.0619-
2CoverCarbon Steel A1051.0460-
3FloatStainless Steel SUS316L1.4404AISI316L
4Orifice---
5Orifice GasketSoft Iron SUYP1.1121AISI1010
6Orifice PlugCast Stainless Steel A351 Gr.CF81.4312-
7Orifice Plug GasketSoft Iron SUYP1.1121AISI1010
8Screen (in/out)Stainless Steel SUS430/3041.4016/1.4301AISI430/304
10Cover GasketGraphite/Stainless Steel SUS316L-/1.4404-/AISI316L

Installation and Piping

INFO

Installation, inspection, maintenance, repairs, disassembly, adjustment and valve opening/closing should be carried out only by trained maintenance personnel.

  1. Before installation, remove all protective seals.
  2. Blow out the inlet piping to remove dirt and oil.
  3. Install the steam trap within the allowable inclination (horizontal) and ensure the arrow mark on the body corresponds with the flow direction.
  4. Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally by gravity. The inlet pipe should be short and have few bends.
  5. Support pipes properly within 800 mm on either side of the trap.
  6. Install a bypass valve to discharge condensate, and isolation valves for maintenance.
  7. Install a check valve at the outlet if connecting to a common condensate return line.

Piping Arrangement:

  • Install a catchpot with the proper diameter.
  • Connect the inlet pipe 25-50 mm above the base of the T-pipe to prevent rust and scale from flowing into the trap.
  • Make sure nothing obstructs the flow of condensate at a blind end.

Inspection and Maintenance

Operational inspections should be performed at least twice per year.

Parts Inspection Procedure
Body, Cover(s)Check inside for damage, dirt, grease, oil film, rust or scale
GasketsCheck for warping or damage
Bimetal PlateCheck for damage
Air Vent Valve (and Seat)Check for damage
Screen(s)Check for clogging, corrosion or damage
FloatCheck for deformation, damage, oil film or water inside
Orifice OpeningCheck for rust, scale, oil film, wear or damage

TIP

Tighten cover nuts to 150 N·m (24 mm across flats) and orifice to 350 N·m (38 mm) for the JH7.2R-B model. Orifice plug should be tightened to 700 N·m (46 mm).

Operational Check

  • Normal: Condensate is discharged continuously with flash steam and the sound of flow can be heard.
  • Blocked: No condensate is discharged. The trap is quiet and surface temperature is low.
  • Blowing: Live steam continually flows from the outlet with a continuous metallic sound.
  • Steam Leakage: Live steam is discharged together with condensate and there is a high-pitched sound.

Troubleshooting

ProblemCauseRemedy
No condensate is discharged (blocked)Float is damaged or filled with condensateReplace float
Orifice, screen or piping are cloggedClean
The bimetal is damagedReplace bimetal
Operating pressure exceeds max specified, or insufficient differential pressureCompare specs and actual conditions
Steam locking has occurredBlowdown through bypass or close inlet valve and allow cooling
Steam is discharged or leaks (blowing)Rust and scale accumulated around valve seat or under floatClean
Orifice is damagedReplace orifice
Float is deformed or coated with scaleClean or replace float
Trap installed above maximum allowable inclinationCorrect installation
Vibration of trapLengthen inlet piping, fasten securely
Bimetal air vent valve surface/seat has build-up or scratchClean or replace bimetal/seat
Steam leaks from other placesDeterioration or damage to gasketsReplace gaskets
Improper tightening torque for coverTighten to proper torque
Float frequently damagedWater hammer occursExamine piping for water hammer causes

Dimensions

TLV JH7.2R-B socket welded dimensions

TLV JH7.2R-B flanged dimensions

  • DN 40, 50 Socket Welded: L = 401 mm, H = 320 mm, H1 = 244 mm, W = 250 mm. Weight: ~35-38 kg.
  • DN 40, 50 Flanged (PN25/40): L = 407-411 mm, H = 320 mm. Weight: 35-40 kg.

Discharge Capacity

TLV JH7.2R-B discharge capacity chart

Capacities are based on continuous discharge of condensate 6 °C below saturated steam temperature. A recommended safety factor of at least 1.5 should be applied.