TLV JH7RH-B Free Float Steam Trap

TLV JH7RH-B low alloy cast steel free float steam trap with thermostatic bimetal air vent. Suitable for medium-size process equipment, superheated and high-pressure applications up to 120 barg.

TLV JH7RH-B Free Float Steam Trap

The TLV JH7RH-B is a reliable and durable low alloy cast steel free float steam trap designed for use on medium-size process equipment. It is suitable for both superheated and extremely high-pressure applications up to 120 barg.

Features

  • Self-modulating free float provides continuous, smooth, low-velocity condensate discharge as process loads vary.
  • Precision-ground float, constant water seal and three-point seating design ensure a steam-tight seal, even under no-load conditions.
  • Thermostatic bimetal air vent valve vents air automatically for rapid startup.
  • Built-in screen with large surface area ensures extended trouble-free operation.
  • Easy, inline access to internal parts simplifies cleaning and reduces maintenance costs.

Options

For higher pressure and temperature applications, the JH7RH-P and JH7RH-W are manufactured with a cover threaded plug or socket connection instead of the bimetal air vent, allowing operation up to 530 °C.

Configuration

TLV JH7RH-B configuration and internal parts diagram

No.DescriptionMaterialDINASTM/AISI
1BodyLow Alloy Cast Steel A217 Gr.WC91.7379-
2CoverLow Alloy Cast Steel A217 Gr.WC91.7379-
3FloatStainless Steel SUS316L1.4404AISI316L
4Orifice---
5Orifice GasketGraphite/Stainless Steel SUS316-/1.4401-/AISI316
6Orifice LocknutStainless Steel SUS3031.4305AISI303
7Outlet Cover GasketGraphite/Stainless Steel SUS309S+cb--
8Outlet CoverStainless Steel SUS420J21.4031AISI420
9Cover BoltAlloy Steel SNB161.7711A193 Gr.B16
10Cover NutAlloy Steel SNB71.7225A193 Gr.B7
11Cover GasketGraphite/Stainless Steel SUS309S+cb--
12Outlet Cover BoltAlloy Steel SNB161.7711A193 Gr.B16
13Outlet Cover NutAlloy Steel SNB71.7225A193 Gr.B7
14ScreenStainless Steel SUS4301.4016AISI430
15Screen HolderStainless Steel SUS3041.4301AISI304
16Snap RingStainless Steel SUS3041.4301AISI304
17Screen Holder RetainerStainless Steel SUS3041.4301AISI304
18NameplateStainless Steel SUS3041.4301AISI304
19Bimetal Air Vent Unit---
20Air Vent GuideStainless Steel SUS3031.4305AISI303
21Air Vent Unit GasketStainless Steel SUS316L1.4404AISI316L

Dimensions

Socket Welded

TLV JH7RH-B socket welded dimensions

DNL (mm)H (mm)H1 (mm)φW (mm)φD (mm)φC (mm)h (mm)Weight (kg)
15390371 (382)27025853.521.81376
20390371 (382)27025853.527.21376
25390371 (382)27025853.533.91376
( ) JH7RH-W

Flanged

TLV JH7RH-B flanged dimensions

DNL (ASME Class 900RF/1500RF) (mm)H (mm)H1 (mm)φW (mm)Weight (kg)
15572371 (382)27025894
20572371 (382)27025895
25572371 (382)27025898
( ) JH7RH-W

Discharge Capacity

TLV JH7RH-B discharge capacity graph

  1. Line numbers within the graph are orifice numbers.
  2. Differential pressure is the difference between the inlet and outlet pressure of the trap.
  3. Capacities are based on continuous discharge of condensate 6 °C below saturated steam temperature.
  4. Recommended safety factor: at least 1.5.

WARNING

DO NOT use traps under conditions that exceed maximum differential pressure, as condensate backup will occur!

Proper Installation

  • Installation, inspection, maintenance, repairs, disassembly, adjustment and valve opening/closing should be carried out only by trained maintenance personnel.
  • Use the eyebolts for removing the cover only; DO NOT use the eyebolts for hoisting the product.
  • Take measures to prevent people from coming into direct contact with product outlets.
  • Install for use under conditions in which no freeze-up will occur.
  • Install for use under conditions in which no water hammer will occur.
  1. Before installation, be sure to remove all protective seals.
  2. Before installing the trap, blow out the inlet piping to remove all dirt and oil.
  3. When hoisting the product, hang the rope around the inlet/outlet as close to the body as possible.
  4. Install the steam trap within the allowable inclination. Also make sure that the arrow mark on the body corresponds with the direction of flow.
  5. Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity. The inlet pipe should be as short and have as few bends as possible.
  6. Support the pipes properly within 800 mm (2.5 ft) on either side of the trap.
  7. Install a bypass valve to discharge condensate, and inlet and outlet valves to isolate the trap in the event of trap failure or when performing maintenance.
  8. Install a check valve at the trap outlet whenever more than one trap is connected to the condensate collection pipeline.
  9. The use of unions is recommended to facilitate connection and disconnection of screwed models.

Inspection and Maintenance

Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.

DANGER

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.

Parts Inspection Procedure

PartInspection Item
Body, Cover(s)Check inside for damage, dirt, grease, oil film, rust or scale
GasketsCheck for warping or damage
Bimetal PlateCheck for damage
Air Vent Valve (and Seat)Check for damage
Screen(s)Check for clogging, corrosion or damage
FloatCheck for deformation, damage, oil film or water inside
Orifice OpeningCheck for rust, scale, oil film, wear or damage

Tightening Torques (JH7RH-B)

PartTorque (N·m)Distance Across Flats (mm)
Cover Nut70046
Outlet Cover Nut20030
Orifice Locknut25032
Air Vent Valve Seat3019
Air Vent Guide10024

Troubleshooting

ProblemCauseRemedy
No condensate is discharged (blocked) or discharge is poorFloat is damaged or filled with condensateReplace the float
Orifice, screen or piping are clogged with rust or scaleClean
The bimetal is damagedReplace with new bimetal
The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differentialCompare specifications and actual operating conditions
Steam locking has occurredBlowdown through the bypass or close the trap inlet valve and allow the trap to cool
Steam is discharged or leaks from the trap outlet (blowing) (steam leakage)Rust and scale have accumulated around the valve seat or under the floatClean
Orifice is damagedReplace with new orifice
Float is deformed or coated with scaleClean or replace the float
Trap is installed above the maximum allowable inclination angleCorrect the installation
Vibration of trap occursLengthen inlet piping, then fasten it securely
The bimetal air vent valve surface and/or the air vent valve seat has a build-up or is scratchedClean or replace with new bimetal and/or air vent valve seat
The bimetal is damagedReplace with new bimetal
Steam leaks from a place other than the trap outletDeterioration of or damage to gasketsReplace the gaskets
Leakage from eroded cavities of body or coverReplace the trap
Improper tightening torque for cover was usedTighten to the proper torque
Float is frequently damagedWater hammer occursExamine the piping for problems that can cause water hammer