TLV JH-X Series JH7RL-X free float steam trap with thermostatic air vent (X-element). Suitable for up to 3.2 MPaG (450 psig) in heat exchangers and process heaters. Discharges condensate continuously.

TLV JH7RL-X inline repairable JH-X series steam traps with thermostatic air vent (X-element) are suitable for a wide range of applications with small-to-large capacities and pressures up to 3.2 MPaG (450 psig), such as all kinds of heat exchangers, process heaters and coils. The traps discharge condensate continuously and automatically, at a temperature slightly lower than saturation temperature. (1 MPa = 10.197 kg/cm², 1 bar = 0.1 MPa)
WARNING
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.
DANGER
Install properly and DO NOT use this product outside the recommended operating pressure, temperature and other specification ranges. Improper use may result in such hazards as damage to the product or malfunctions, which may lead to serious accidents.

| No. | Description | No. | Description |
|---|---|---|---|
| 1 | Body | 15 | X-element Guide |
| 2 | Cover | 16 | Air Vent Valve Seat |
| 3 | Cover Gasket | 17 | Spring Clip |
| 4 | Float | 18 | Flange or Socket |
| 5 | Orifice | 19 | Nameplate |
| 6 | Orifice Gasket | 20 | Float Cover |
| 7 | Orifice Plug | 21 | Drain Plug |
| 8 | Plug Gasket | 22 | Drain Plug Gasket |
| 9 | Screen | 23 | Screen Holder |
| 10 | Cover Bolt | 24 | Snap Ring |
| 11 | Cover Nut | 26 | Screen Holder Retainer |
| 12 | Connector | 27 | X-element Case |
| 13 | Connector Gasket | 28 | X-element Screen |
| 14 | X-element | 29 | Eye Bolt |
INFO
Maximum allowable pressure (PMA) and maximum allowable temperature (TMA) are PRESSURE SHELL DESIGN CONDITIONS, NOT OPERATING CONDITIONS.
To avoid malfunctions, product damage, accidents or serious injury, install properly and DO NOT use this product outside the specification range. Local regulations may restrict the use of this product to below the conditions quoted.

| Requirement | Correct Execution | Incorrect Execution |
|---|---|---|
| Install a catchpot with the proper diameter. | Diameter is properly sized to handle condensate load. | Diameter is too small. |
| Make sure the flow of condensate is not obstructed. | Unobstructed piping path directly to the trap. | Diameter is too small and inlet protrudes into pipe. |
| Prevent rust and scale from flowing into the trap. | Connect the inlet pipe 25 - 50 mm (1 - 2 in) above the base of the T-pipe. | Rust and scale flow directly into the trap with the condensate. |
| Blind end installations. | Make sure nothing obstructs the flow of condensate into the trap. | Condensate collects in the pipe without reaching the trap. |
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.
| Parts | Inspection Procedure |
|---|---|
| Body, Cover(s) | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| X-element | Check for damage |
| Screen(s) | Check for clogging, corrosion or damage |
| Float | Check for deformation, damage, oil film or water inside |
| Air Vent Valve Seat, Orifice | Check for rust, scale, oil film, wear or damage |
Maintenance parts and repair parts are available from TLV in kits. Maintenance Kits (M) generally include items like Cover Gasket, Orifice Gasket, and Plug Gasket. Repair Kits (R) typically include the Orifice, Float, and specialized replacement elements in addition to the gaskets.
A visual inspection can be carried out to aid in determining the necessity for immediate maintenance or repair, if the trap is open to atmosphere.
| Condition | Indicator |
|---|---|
| Normal | Condensate is discharged continuously with flash steam and the sound of flow can be heard. If there is very little condensate, there is almost no sound of flow. |
| Blocked | No condensate is discharged. The trap is quiet and makes no noise, and the surface temperature of the trap is low. |
| Blowing | Live steam continually flows from the outlet and there is a continuous metallic sound. |
| Steam Leakage | Live steam is discharged through the trap outlet together with the condensate and there is a high-pitched sound. |
If the expected performance is unachievable after installation of the steam trap, check the following points for appropriate corrective measures.
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping are clogged with rust or scale | Clean | |
| X-element is damaged | Replace the X-element | |
| Operating pressure exceeds max specified pressure, or insufficient differential pressure | Compare specifications and actual operating conditions | |
| Steam locking has occurred | Blowdown through bypass or close inlet valve to cool | |
| Steam is discharged or leaks from outlet (blowing/leakage) | Rust and scale accumulated around orifice or under float | Clean |
| Orifice is damaged | Replace with new orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap installed above maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, fasten securely | |
| X-element is damaged, or clogged with rust/scale | Clean or replace the X-element | |
| Steam leaks from other locations | Gaskets deteriorated or damaged | Replace with new gaskets |
| Improper tightening torques | Tighten to proper torque | |
| Valve body or cover is corroded | Replace the trap | |
| Float is frequently damaged | Water hammer occurs | Check piping to correct water hammer causes |