TLV SJ3FNB / SJ3FVB Free Float Steam Trap with Thermostatic Air Venting

TLV SJ3FNB and SJ3FVB ductile cast iron free float steam traps with thermostatic bimetal air venting. Features three-point seating, up to 22 barg PMO, and 220°C TMO.

TLV SJ3FNB / SJ3FVB Free Float Steam Trap with Thermostatic Air Venting

TLV SJ3FNB and SJ3FVB are reliable and durable ductile cast iron free float steam traps with tight shut-off for use on small to medium process equipment. The SJ3FNB is designed for horizontal piping installation, while the SJ3FVB is designed for vertical piping installation. They feature an integral plate-type bimetal air vent unit for rapid startup.

The self-modulating free float provides continuous, smooth, low velocity condensate discharge as process loads vary. A precision-ground float, constant water seal, and three-point seating design ensure a steam-tight seal, even under no-load conditions. The built-in screen with a large surface area ensures extended trouble-free operation, and easy, inline access to internal parts simplifies cleaning and reduces maintenance costs.

Specifications and Materials

No.DescriptionMaterialDINASTM/AISI
1BodyDuctile Cast Iron GGG40.30.7043A395 Gr.60-40-18
2CoverDuctile Cast Iron GGG40.30.7043A395 Gr.60-40-18
3FloatStainless Steel SUS316L1.4404AISI316L
5Orifice GasketFluorine Resin PTFEPTFEPTFE
6ScreenStainless Steel SUS3041.4312AISI304
8Cover GasketFluorine Resin PTFEPTFEPTFE
17Bimetal Plate---

WARNING

To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range. Local regulations may restrict the use of this product to below the conditions quoted. Maximum allowable pressure (PMA) and maximum allowable temperature (TMA) are PRESSURE SHELL DESIGN CONDITIONS, NOT OPERATING CONDITIONS.

Dimensions

SJ3FNB Flanged (Horizontal)

TLV SJ3FNB / SJ3FVB Horizontal Flanged Dimensions

DN (DIN 2501 PN25/40)L (mm)H (mm)W (mm)B (mm)Weight (kg)
151501601801006.0
201501601801006.4
251601601851006.9

SJ3FVB Flanged (Vertical)

TLV SJ3FNB / SJ3FVB Vertical Flanged Dimensions

DN (DIN 2501 PN25/40)L (mm)W1* (mm)B1* (mm)Weight (kg)
15150155705.1
20150155705.6
25160155706.3

(Approximate values)

Discharge Capacity

TLV SJ3FNB / SJ3FVB Discharge Capacity Graph

INFO

  1. Line numbers within the graph are orifice numbers.
  2. Differential pressure is the difference between the inlet and outlet pressure of the trap.
  3. Capacities are based on continuous discharge of condensate 6°C below saturated steam temperature.
  4. Recommended safety factor: at least 1.5.

Configuration

SJ3FNB (Horizontal)

TLV SJ3FNB / SJ3FVB Horizontal Configuration

SJ3FVB (Vertical)

TLV SJ3FNB / SJ3FVB Vertical Configuration

Proper Installation and Piping

  1. Before installation, be sure to remove all protective seals.
  2. Install the steam trap within the allowable inclination. Make sure that the arrow mark on the body corresponds with the direction of flow.
  3. Before installing the trap, blow out the inlet piping to remove all dirt and oil.
  4. Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity. The inlet pipe should be as short and have as few bends as possible.
  5. Support the pipes properly within 800 mm (2.5 ft) on either side of the trap.
  6. Install a bypass valve to discharge condensate, and inlet and outlet valves to isolate the trap in the event of trap failure or when performing maintenance.
  7. Install a check valve at the trap outlet whenever more than one trap is connected to the condensate collection pipeline.

Piping Arrangement Checklist

  • Install a catchpot with the proper diameter.
  • Make sure the flow of condensate is not obstructed.
  • To prevent rust and scale from flowing into the trap, connect the inlet pipe 25 - 50 mm (1 - 2 in) above the base of the T-pipe.
  • When installing on the blind end, make sure nothing obstructs the flow of condensate.

Inspection and Maintenance

Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.

DANGER

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.

PartInspection Procedure
Body, CoverCheck inside for damage, dirt, grease, oil film, rust or scale
GasketsCheck for warping or damage
Bimetal UnitCheck for damage
ScreenCheck for clogging, corrosion or damage
FloatCheck for deformation, damage, oil film or water inside
Air Vent Valve Seat, OrificeCheck for rust, scale, oil film, wear or damage

Tightening Torques (SJ3FNB / SJ3FVB)

PartTorque (N·m)Distance Across Flats (mm)
Cover Bolt6016, 17
Orifice4017
Screen Holder14024 (SJ3FNB) / 38 (SJ3FVB)
Drain Plug3012
Element Cover14032
Air Vent Valve Seat3519
Orifice Plug (SJ3FNB)14038

Troubleshooting

If the expected performance is unachievable after installation, check the following points:

ProblemCauseRemedy
No condensate is discharged or discharge is poorFloat is damaged or filled with condensateReplace the float
Orifice, screen or piping is clogged with rust or scaleClean
Steam-locking has occurredBlowdown through the bypass or close the trap inlet valve and allow the trap to cool
Bimetal element is damagedReplace the bimetal unit
Operating pressure exceeds maximum specified pressure, or insufficient differential pressureCompare specifications and actual operating conditions
Steam is discharged or leaks from the trap outletRust and scale have accumulated around the orifice or under the floatClean
Orifice is damagedReplace the orifice
Float is deformed or coated with scaleClean or replace the float
Trap is installed above the maximum allowable inclination angleCorrect the installation
Vibration of trap occursLengthen inlet piping, then fasten it securely
Steam leaks from a place other than the trap outletDeterioration of or damage to gasketsReplace with new gaskets
Improper tightening torque for cover was usedTighten to the proper torque