Yoshitake AL-31, AL-31H Safety Relief Valve Closed Type

Yoshitake AL-31 and AL-31H full-bore safety relief valves. Stainless steel closed type with dash-pot structure, suitable for steam, air, water, and oil. Set pressure up to 2.0 MPa.

Yoshitake AL-31, AL-31H Safety Relief Valve Closed Type

Yoshitake AL-31 and AL-31H are full-bore safety relief valves designed with a closed type structure and made entirely of stainless steel. They offer high corrosion resistance and durability. The AL-31H model can be set at a maximum of 2.0 MPa. These valves are suitable for steam, air, cold and hot water, oil, and other non-dangerous fluids.

Yoshitake AL-31 product photo

Features

  • Safety relief valve of all stainless steel made, offering high corrosion resistance and durability in particular.
  • AL-31H can be set at Max. 2.0 MPa.
  • Dash-pot structure.
  • Non-leakage design.

Specifications

INFO

The maximum temperature is 150°C when using for water, oil, or other liquids.

Dimensions and Weights

Yoshitake AL-31 dimensions diagram

Nominal Sizedi × D × do (mm)L (mm)H1 (mm)H (mm)Flow Area (mm²)Weight (kg)
15A15×16×20737216020.13.4
20A20×21×25777416334.64.5
25A25×26×32918718753.06.5
32A32×33×40969223885.58.1 (8.3)
40A40×41×50114100277132.011.4 (11.7)
50A50×51×65116107315 (357)204.215.0 (18.0)

INFO

  • The above values in parentheses are the dimensions and weights of JIS 20K RF flanged.
  • Screwed connection size of the outlet side is 1 size larger than the nominal size.

Structure and Drawings

Yoshitake AL-31 structural drawingYoshitake AL-31 specification table drawingYoshitake AL-31 internal structure diagram

Part NumberPart Name
3Valve Seat
4Valve
6Spring
9Adjusting Screw
11Cap
17Pressure Groove

Blowout Operation

As the inlet pressure approaches the blowout pressure, the force of fluid pushing up the valve approaches the force of the spring pressing down the valve. The safety relief valve commences to blow when the inlet pressure reaches around 3% below the blowout pressure. The fluid accumulates gradually on the pressure groove and when the fluid pressure reaches the blowout pressure the valve pops.

Closing Operation

Since the inlet pressure of the safety relief valve decreases when the fluid is released into the atmosphere by the pop action of the valve, the force of fluid lift is lowered. At this point, the repelling force of the spring becomes larger than the force of fluid lift and thus the valve closes. In addition, while the safety relief valve discharges, pressure of fluid entering into the back of the valve (back pressure) adds to the closing force.

Certified Capacity Tables (Partial)

::: note The following capacity tables provide values for sizes 15A through 32A. Values for 40A and 50A have been omitted due to source document truncation. :::

AL-31 for Steam (Saturation Temperature)

Capacity in kg/h

Nominal Size0.05 MPa0.1 MPa0.2 MPa0.3 MPa0.4 MPa0.5 MPa0.6 MPa0.7 MPa0.8 MPa0.9 MPa1.0 MPa
15A152029405060708090100109
20A2735516987104121138155172189
25A425478105133159186212237263289
32A6787127170215257300342383425467

AL-31H for Steam (Saturation Temperature)

Capacity in kg/h

Nominal Size1.0 MPa1.1 MPa1.2 MPa1.3 MPa1.4 MPa1.5 MPa1.6 MPa1.7 MPa1.8 MPa1.9 MPa2.0 MPa
15A109119129139149158168178188198207
20A189206222239256273290306324340357
25A289315341367393418444470496522547
32A467509550592634675716758800842883

AL-31 for Air (20°C)

Capacity in kg/h

Nominal Size0.05 MPa0.1 MPa0.2 MPa0.3 MPa0.4 MPa0.5 MPa0.6 MPa0.7 MPa0.8 MPa0.9 MPa1.0 MPa
15A253348658198114131147164181
20A445783111140169197226254283311
25A6787127171215258302346390433477
32A108141205276347417488558629699770

AL-31H for Air (20°C)

Capacity in kg/h

Nominal Size1.0 MPa1.1 MPa1.2 MPa1.3 MPa1.4 MPa1.5 MPa1.6 MPa1.7 MPa1.8 MPa1.9 MPa2.0 MPa
15A181197214230247264280297313330347
20A311340368397426454483511540568597
25A477521565608652696740783827871915
32A7708419119821052112311931264133514051476

AL-31 for Water (at 20°C, accumulation: 25%)

Capacity in m³/h

Nominal Size0.05 MPa0.1 MPa0.2 MPa0.3 MPa0.4 MPa0.5 MPa0.6 MPa0.7 MPa0.8 MPa0.9 MPa1.0 MPa
15A0.20.30.50.60.70.80.80.91.01.01.1
20A0.40.60.81.01.21.31.51.61.71.81.9
25A0.60.91.31.61.82.12.32.52.62.82.9
32A1.01.52.12.63.03.43.74.04.34.54.8

AL-31H for Water (at 20°C, accumulation: 25%)

Capacity in m³/h

Nominal Size1.0 MPa1.1 MPa1.2 MPa1.3 MPa1.4 MPa1.5 MPa1.6 MPa1.7 MPa1.8 MPa1.9 MPa2.0 MPa
15A1.11.11.21.21.31.31.41.41.51.51.6
20A1.92.02.12.22.32.32.42.52.62.62.7
25A2.93.13.23.43.53.63.73.94.04.14.2
32A4.85.05.25.55.75.96.16.26.46.66.8

Installation and Piping

WARNING

  • Do not install any closing device such as a stop valve at inlet or outlet sides of the product.
  • Do not apply the product to devices which do not allow any valve seat leakage. This product allows valve seat leakage and does not close completely.
  • Do not disassemble the product.
  • Install an exhaust pipe on outlet side of the product, and lead it to a place where there is no risk of physical damage even if fluid blows out.

Yoshitake AL-31 piping example

Pipe Mount

  • Pipe mount should have sufficient strength and rigidity against stress which are induced by reaction force in opposite direction of the exhaust through the axis of the exhaust pipe.
  • To prevent pressure loss from decreasing discharge volume and causing unstable operation, install the product vertically as close as possible to the can body and the header.
  • Inner diameter of pipe mount shall be more than that of the product inlet.

Exhaust Pipe

  • Install exhaust pipe and drip pan elbow so that the product cannot be subject to the stress caused by thermal expansion of equipment and by dilatation of the exhaust pipe due to thermal action of blowout.
  • Inner diameter of exhaust pipe shall be more than that of the product outlet to avoid improper back pressure.

Maintenance

TIP

Daily Inspection: Check for corrosion or cracks, leakage from the product under normal working pressure, and leakage from joints between the product and piping. Monthly Inspection: Check that there is no loose piping at the inlet and outlet side, and that the cap is fastened securely. Check the operation by raising fluid pressure to the set pressure.