Yoshitake STC-1 steam trap checker. Features automatic diagnosis, surface temperature measurement (0-300°C), and auscultation mode. Speedy 2-8s diagnosis with LCD and LED indicators.

Yoshitake STC-1 is a simple checker that diagnoses the condition of steam traps. It is equipped with automatic steam trap diagnosis, operation auscultation, and steam piping surface temperature sensor functions, enabling speedy and accurate evaluation in various environments.

| Specification | Value |
|---|---|
| Model | STC-1 |
| Steam trap automatic diagnosis time | 2 seconds or 8 seconds |
| Working pressure for automatic diagnosis | 0.05 - 8.0 MPa |
| Working temperature for surface sensing | 0 - 300 °C |
| Ambient temperature | 0 - 40 °C (Non-Freezing) |
| Automatic power off | After 5 minutes (while in diagnosis mode and not in operation) |
| Where to use | Inside and outside (should not be exposed to rain water) |
| Battery | DC1.5V AAA alkaline batteries 2pcs |
| Continuous operating time | Approximately 8 hours |
| Weight | 214g (including batteries) / 235g (without batteries in some regions) |
| Accessories | Storage case, sensor cap, earphones |

| Mode (Function) | Overview |
|---|---|
| Steam trap automatic diagnosis mode | Automatically diagnoses the conditions of steam traps. |
| Surface temperature sensor mode | Indicates the surface temperature of steam piping. |
| Auscultation mode | Listens to the conditions of the steam trap. |
| Result | Working conditions of steam trap | LED color |
|---|---|---|
| GOOD | Good condition | Green |
| CAUTION | Hard to judge whether GOOD or LEAK. Caution required for the possibility of LEAK. | Yellow |
| LEAK | High possibility of steam leakage | Red |
| LOW TEMP. | High possibility of clogged, not in service, or inadequately low capacity, because the surface temperature is low. | Yellow |

| Manual operation button | Operation description |
|---|---|
| POWER/MODE button | Power ON/OFF: Press down the button for 2 seconds or more. Switch the mode: Steam trap automatic diagnosis → Surface temperature sensor → Auscultation |
| TRAP Button | Select a steam trap type: DISC → BUCKET → FLOAT → THERMO → OTHERS |
| ▲·▼ Button | Select a pressure range. Adjust Volume. Back light ON/OFF. |
| START Button | Start steam trap automatic diagnosis. |
WARNING
STC-1 cannot be used to check steam traps for tracing lines.

| No. | Name of Parts | Materials | Q.TY |
|---|---|---|---|
| 1 | Body | Synthetic Resin etc | 1 |
| 2 | Sensor Cap | Synthetic Resin | 1 |
| 3 | Battery Cover | Synthetic Resin | 1 |
| 4 | Battery Cover Gasket | Silicone Rubber | 1 |
| 5 | Rubber Cap | Silicone Rubber | 1 |
| 6 | Product Label | - | 1 |
| 7 | Serial Number Label | - | 1 |
| 8 | Earphone | - | 1 |
| 9 | Alkaline Battery | - | 2 |
| 10 | Carry Case | - | 1 |
| No | Pressure Range |
|---|---|
| 1 | 0.05 MPa or more and less than 0.1 MPa |
| 2 | 0.1 MPa or more and less than 0.5 MPa |
| 3 | 0.5 MPa or more and less than 1.0 MPa |
| 4 | 1.0 MPa or more and less than 2.0 MPa |
| 5 | 2.0 MPa or more and less than 3.0 MPa |
| 6 | 3.0 MPa or more and less than 4.0 MPa |
| 7 | 4.0 MPa or more and less than 5.0 MPa |
| 8 | 5.0 MPa or more and less than 6.0 MPa |
| 9 | 6.0 MPa or more and less than 7.0 MPa |
| 10 | 7.0 MPa or more and less than 8.0 MPa |


TIP
During the steam trap diagnosis, press the sensor tip as vertically as possible. If the sensor tip is pressed from an angle, the contact condition will change and accurate measurement will not be possible. It is recommended to create a flat surface by sanding the measurement surface.