BURKERT Type 3361 electromotive 2-way globe control valve features dynamic closed-loop control, positioning speeds up to 6 mm/s, and IP65/IP67 protection.

BURKERT Type 3361 electromotive 2-way globe control valve provides highly precise, dynamic closed-loop control for demanding operating conditions. The electromotive actuator with a ball screw positions the control cone with a positioning speed of up to 6 mm/s, reacting almost delay-free to process signals. Pressure variations or shocks in the medium are not transferred to the valve position. Each flow-optimized valve body can be equipped with up to 5 different valve seats for precise adaptation to specific flow requirements. The closed design features an IP65/IP67 degree of protection and high impact and vibration resistance.
| Product properties | Specification |
|---|---|
| Design | Globe control valve |
| Nominal diameter | DN 10 to DN 100, NPS 3/8 to 4 |
| Safety setting (power failure) | With SAFEPOS energy-pack: open, closed or freely programmable. Without: blocked in last position |
| Flow direction | Against closing direction (below seat) |
| Controller variant | Positioner or process controller (option) |
| Operating pressure | 0 to 25 bar(g), 40 bar(g) on request. Vacuum variant down to -0.9 bar(g) |
| Nominal pressure | PN 25/PN 40 (DIN EN 1333), Class 150 (DIN EN 1759) |
| Kv value | 0.1 to 140 m³/h |
| Flow characteristic | Equal percentage, linear (on request) |
| Seat leakage | Class III, IV and VI (DIN EN 60534-4) |
| Closing time | AG2: 3.3 to 6.6 s; AG3: 8.7 to 12.0 s |
| Travel speed | 6 mm/s (AG2 1300 N), 4 mm/s (AG2 2500 N), 3 mm/s (AG3 7700/10000 N) |
| Dead band | ± 0.1 % |
| Operating voltage | 24 V DC ± 10 % (maximum residual ripple 10 %) |
| Medium temperature | -40 °C to +230 °C |
| Ambient temperature | -25 °C to +65 °C (without additional modules) |
Approvals and Conformities
The Type 3361 is available with optional approvals including ATEX/IECEx (Zone 2/22), UL Listing for USA/Canada, FDA and USP Class VI compliance for food and beverage applications, and suitability for oxygen or hydrogen media.

| Component | Material (AG2 / AG3) |
|---|---|
| Display housing/blind cover | PPS (standard), stainless steel 1.4301 (for ATEX/IECEx) |
| Actuator cover | PPS (AG2) / PC (AG3) |
| Seal | EPDM |
| Actuator housing | Powder-coated aluminium |
| Actuator base | PPS (AG2) / Stainless steel 1.4308 (AG3) |

| Component | Material |
|---|---|
| Spindle | Stainless steel 1.4401 (316)/1.4404 (316L) |
| Spindle seal | PTFE V-seals (filled) with spring compensation |
| Valve body | Stainless steel CF3M |
| Seat seal | Stainless steel 1.4571 (optionally hardened), PTFE or PEEK seal washer |
| Control cone | Stainless steel 1.4571 (optionally hardened) |
The valve features an equal-percentage flow characteristic according to DIN EN 60534-2-4 (linear characteristic curve available on request). The theoretical rangeability reaches up to 50:1 depending on the seat size.

| Tight sealing required | Leakage class | Medium temperature | Seat seal |
|---|---|---|---|
| No (Additional shut-off valve recommended) | III/IV (metal seals) | -40 °C to +230 °C | Stainless steel |
| Yes (Additional shut-off valve often unnecessary) | VI (soft seals) | -40 °C to +130 °C | PTFE |
| Yes | VI (soft seals) | -10 °C to +230 °C | PEEK |
The electromotive linear drive consists of a brushless DC motor, a gear, and a spindle system that transfers the force to the closing element. The integrated electronics are controlled either by standard analogue signals or via a digital fieldbus (EtherNet/IP, PROFINET, Modbus TCP, EtherCAT).

Integrated Position Controller
The position of the actuator (stroke) is controlled according to the position set-point value. The displacement transducer records the actual position of the electric linear actuator, and the positioner compares this with the set-point value to adjust the motor drive accordingly.
Safety Position via Energy Storage
The safety starting positions in case of power interruption are realized with the optional SAFEPOS energy-pack. The desired position (open, closed, or intermediate) is set via the menu. Without the energy storage, the valve remains in its last position upon power failure.
Explore similar products in our catalog