TLV SJH6NB inline repairable free float steam trap with thermostatic air vent (X-element). Designed for continuous condensate discharge in heat exchangers, tank heaters, and process equipment up to 32 barg.

TLV SJH6NB inline repairable free float steam trap with thermostatic air vent (X-element) is suitable for a wide range of applications with small-to-large capacities and pressures up to 32 barg, such as heat exchangers, tank heaters, dryers, and process equipment. The trap discharges condensate continuously and automatically, at a temperature slightly lower than saturation temperature.
WARNING
NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or damage to property and equipment.


| No. | Name |
|---|---|
| 1 | Body |
| 2 | Cover |
| 3 | Float |
| 4 | Orifice |
| 5 | Orifice Gasket |
| 6 | Orifice Plug Gasket |
| 7 | Orifice Plug |
| 8 | Cover Gasket |
| 9 | Cover Bolt |
| 10 | Cover Nut |
| 11 | Screen Holder Gasket |
| 12 | Screen Holder |
| 13 | Main Screen |
| 14 | Element Cover Gasket |
| 15 | Element Cover |
| 16 | Element Guide |
| 17 | Air Vent Valve Seat |
| 18 | Bimetal Plate |
| 19 | Snap Ring |
| 20 | Air Vent Valve |
| 21 | Spring Clip |
| 22 | Air Vent Screen |
| 23 | Nameplate |
Maximum Allowable Inclination

Check to make sure that the pipes connected to the trap have been installed properly.
| Requirement | Correct | Incorrect |
|---|---|---|
| Install a catchpot of the proper diameter. | Ensure proper sizing | Diameter is too small. |
| Make sure the flow of condensate is not obstructed. | Flush with pipe bottom | Diameter is too small and inlet protrudes into pipe. |
| To prevent rust and scale from flowing into the trap, connect the inlet pipe 25 - 50 mm (1 - 2 in) above the base of the T - pipe. | Elevated connection | Rust and scale flow into the trap with the condensate. |
| When installing on the blind end, make sure nothing obstructs the flow of condensate. | Unobstructed flow | Condensate collects in the pipe. |
A visual inspection can be carried out to aid in determining the necessity for immediate maintenance or repair, if the trap is open to atmosphere. If the trap does not discharge to atmosphere, use diagnostic equipment.
| Condition | Description |
|---|---|
| Normal | Condensate is discharged continuously with flash steam and the sound of flow can be heard. If there is very little condensate, there is almost no sound of flow. |
| Blocked | No condensate is discharged. The trap is quiet and makes no noise, and the surface temperature of the trap is low. |
| Blowing | Live steam continually flows from the outlet and there is a continuous metallic sound. |
| Steam Leakage | Live steam is discharged through the trap outlet together with the condensate and there is a high-pitched sound. |
Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.

Parts Inspection Procedure
| Part | Procedure |
|---|---|
| Body, Cover(s) | Check inside for damage, dirt, grease, oil film, rust or scale |
| Gaskets | Check for warping or damage |
| X-element / Screen(s) | Check for damage, clogging, or corrosion |
| Float | Check for deformation, damage, oil film or water inside |
| Air Vent Valve Seat, Orifice | Check for rust, scale, oil film, wear or damage |
If the expected performance is unachievable after installation of the steam trap, check the following points for appropriate corrective measures.
| Problem | Cause | Remedy |
|---|---|---|
| No condensate is discharged (blocked) or discharge is poor | Float is damaged or filled with condensate | Replace the float |
| Orifice, screen or piping is clogged with rust or scale | Clean | |
| X-element is damaged | Replace the X-element | |
| The trap operating pressure exceeds the maximum specified pressure | Compare specifications and actual operating conditions | |
| Steam-locking has occurred | Blow down through the bypass or allow the trap to cool | |
| Steam is discharged or leaks from the trap outlet (blowing) | Orifice is clogged, or rust and scale have accumulated under the float | Clean |
| Orifice is damaged | Replace the orifice | |
| Float is deformed or coated with scale | Clean or replace the float | |
| Trap is installed above the maximum allowable inclination angle | Correct the installation | |
| Vibration of trap occurs | Lengthen inlet piping, then fasten it securely |
The seal on the threaded plugs/holders found on TLV products is formed by a flat metal gasket. The gasket may be pinched in the thread recesses during assembly if not handled correctly.