Skip to content
Max Pressure 1.0 MPaCold & Hot Water

Yoshitake CF-60 Constant Flow Valve

Yoshitake CF-60 constant flow valve for water supply lines. Features 1.0 MPa maximum pressure, 0.2-0.8 MPa working differential pressure, and bronze body. Available in screwed and wafer connections.

Yoshitake CF-60 Constant Flow Valve

Yoshitake CF-60 is a constant flow valve used in the water supply lines of apartment buildings and medium-high rise buildings. The orifice opening is adjusted to keep the flow rate constant in response to pressure fluctuation on the primary side. The product conforms to the standard of the Japanese Water Supply Act and is NPb-treated, making it suitable for cold and hot water applications up to 60°C (and up to 90°C for hot water supply, as noted in the catalog).

Yoshitake CF-60 constant flow valve

Specifications

ModelCF-60
Nominal size25-50A65-100A
ApplicationCold and hot water
Max. pressure1.0 MPa
Working differential pressure range0.2-0.8 MPa
Application temperature5-60°C
Set flow rate20 L/min - 270 L/min100 L/min - 1000 L/min
Tolerance of set flow rateWithin ±20% of set flow rate
ConnectionJIS Rc screwedFlangeless (wafer type)
Installation postureHorizontal or vertical installation

INFO

Connectable flange standard for wafer type (65A - 100A): JIS 5K FF, JIS 10K FF, ANSI 150lb, BSEN PN10/16.

Set Flow Rate and Cartridge Details

Nominal sizeConnectionSet flow rate and Color of cartridge
25AScrewed type20 L/min (Green), 30 L/min (Yellow), 38 L/min (Black), 50 L/min (Red), 70 L/min (Light Blue)
32AScrewed type20 L/min (Green), 30 L/min (Yellow), 38 L/min (Black), 50 L/min (Red), 70 L/min (Light Blue), 100 L/min (Black w/Hole)
40AScrewed type40 L/min (Green), 50 L/min (White), 60 L/min (Yellow), 75 L/min (Black), 100 L/min (Red), 140 L/min (Light Blue), 180 L/min (Blue w/Hole)
50AScrewed type60 L/min (Green), 75 L/min (White), 90 L/min (Yellow), 115 L/min (Black), 150 L/min (Red), 210 L/min (Light Blue), 270 L/min (Blue w/Hole)
65AWafer type100 L/min (Green), 125 L/min (White), 150 L/min (Yellow), 190 L/min (Black), 250 L/min (Red), 350 L/min (Light Blue), 450 L/min (Blue w/Hole)
80AWafer type140 L/min (Green), 210 L/min (Yellow), 260 L/min (Black), 350 L/min (Red), 490 L/min (Light Blue), 630 L/min (Blue w/Hole), 700 L/min (Black w/Hole)
100AWafer type250 L/min (White), 300 L/min (Yellow), 350 L/min (Orange), 500 L/min (Red), 700 L/min (Light Blue), 900 L/min (Blue w/Hole), 1000 L/min (Black w/Hole)

There are two types of black cartridge:

  • Black (The central hollow does not penetrate)
  • Black w/Hole (A hole penetrates in the center)

Structure, Dimensions and Weight

Screwed type (25A-50A)

Yoshitake CF-60 screwed type structure

Nominal sizedL (mm)A (mm)Weight (kg)
25ARc 157410.4
32ARc 1-1/461500.6
40ARc 1-1/263581.0
50ARc 277701.4

Wafer type (65A-100A)

Yoshitake CF-60 wafer type structure

Nominal sizeL (mm)A (mm)B (mm)Weight (kg)
65A131471151.0
80A131581261.2
100A131781461.5

Performance Characteristic Chart

Yoshitake CF-60 noise characteristic chart(The chart shows the noise level at the max. flow rate of each nominal size.)

Yoshitake CF-60 flow rate characteristic chart

Precautions for Installation

WARNING

  • Before installing, remove foreign substances and scale from the piping. Seal materials must not flow into the inside of the product or piping. Commingling of foreign substances leads to malfunction.
  • Install pipes so that excessive load, torque or vibration is not applied to the product.
  • When using this product, running sounds occur. Install it as far away as possible from places where low noise is required.
  • Install a strainer (mesh size of 60 or 80) at the inlet side of the product to prevent scale and dust from causing product failures.
  • The products cannot be used with pipe end core.

To install the product, check the direction of the product so that the fluid flowing and the mark on the product are in the same direction:

  • For screwed connection, the arrow is shown on the label.
  • For wafer connection, "IN/OUT" is shown on the fin.

On installation of wafer types, align center part of the product with that of flange by making fin-shaped part contact with bolt as indicated below:

Yoshitake CF-60 wafer type installation

When installing a constant water level valve or other valve on the outlet side of this product, select a valve that will ensure the required flow rate and pressure, or adjust that valve correctly.

Yoshitake CF-60 outlet side installation

INFO

Flanges, bolts, nuts, and gaskets required for wafer type installation are not included. When using flanges, prepare bolts with appropriate dimensions, taking into account the combined thickness of the product and gasket (19 mm).

Yoshitake CF-60 bolt dimensions for wafer type

Precautions for Operation and Maintenance

TIP

  • Before leading fluid, make sure that there is no danger when the fluid flows to the end of piping.
  • Close the stop valves before and after the valve, and remove all foreign matter and scales via the by-pass line before operation.
  • If case of a possible frozen line, take proper measures to remove water inside the piping or equip the product with insulating materials.
  • Completely discharge the fluid inside of the product and line before leaving the product not operated for a long time to prevent rust.

Troubleshooting

TroubleCauseRemedy
No flow or Poor flowCartridge is clogged or broken; Wrong set flow rate; Frozen; Differential pressure out of specified rangeClean or replace cartridge; Confirm flow rate; Check piping; Review usage conditions
Flow rate more than specifiedCartridge is broken or O-ring hardened; Wrong set flow rate; Differential pressure out of specified rangeReplace product; Confirm flow rate; Review usage conditions
Steam/Fluid leakageParts or body damaged/deformed; Installation on piping is looseReplace product; Retighten