The Yoshitake GD-26S-NE is a direct-type pressure reducing valve made of cast stainless steel. Features a pressure balance structure, reduced noise, and JWWA approval for cold and hot water applications.

Yoshitake GD-26S-NE is a direct-type pressure reducing valve designed for cold and hot water applications. Constructed with corrosion-resistant cast stainless steel wetted parts, it prevents the generation of rusty water. The valve is equipped with a built-in strainer (for 15A to 50A nominal sizes) and features a pressure balance structure that keeps the reduced pressure constant without being affected by fluctuations in the inlet pressure.
The GD-26S-NE model conforms to the standard of the Japanese Water Supply Act (JWWA approval). Its compact and lightweight design makes piping works easy, and its closed structure ensures that fluid is kept inside even if the diaphragm is damaged or broken. Maintenance and inspection can be easily conducted by disassembling simply from the upper side.


Caution
Before installing the product in the piping, be sure to remove foreign substances and scale from the piping. Keep foreign substances from entering the piping, including seal tape or liquid seal agent for piping connection. Ingress of foreign substances, scale or seal agent into the product leads to valve leakage or malfunction of the product.
Note
The set pressure may be affected by ambient temperature (external temperature) and fluid temperature. Install pipes so that the product may not be exposed to direct sunlight.
| Nominal size | d | L | H | H1 | Weight (kg) |
|---|---|---|---|---|---|
| 20A | Rc 3/4 | 135 | 170 | 41 | 2.2 |
| 25A | Rc 1 | 135 | 170 | 41 | 2.2 |
| 32A | Rc 1-1/4 | 180 | 224 | 57 | 4.7 |
| 40A | Rc 1-1/2 | 180 | 224 | 57 | 4.5 |
| 50A | Rc 2 | 200 | 239.5 | 61 | 6.5 |

If the differential pressure before and after the valve is 0.15 MPa or more:
| Nominal size | 15A | 20A | 25A | 32A | 40A | 50A |
|---|---|---|---|---|---|---|
| Rated flow rate L/min | 30 | 40 | 60 | 100 | 150 | 250 |
If the differential pressure before and after the valve is less than 0.15 MPa, use the nominal size selection charts.


| Nominal size | Pressure range | Reduced pressure range | Offset pressure |
|---|---|---|---|
| 15-100A | A | 0.05-0.35 MPa | Within 0.05 MPa |
| 15-100A | B | 0.30-0.70 MPa | Within 0.10 MPa |
Explore similar products in our catalog