Yoshitake GD-27S-NE Pressure Reducing Valve for Cold and Hot Water

The Yoshitake GD-27S-NE is a direct-acting, internal sensing pressure reducing valve for cold and hot water. Features cast stainless steel construction, JIS 10K FF flanged connection, and JWWA approval.

Yoshitake GD-27S-NE Pressure Reducing Valve for Cold and Hot Water

Yoshitake GD-27S-NE is a direct-acting, internal sensing diaphragm pressure reducing valve designed for cold and hot water applications. This valve features a robust cast stainless steel body and FKM valve disc, ensuring durability and zero valve leakage. It utilizes a pressure balance structure to maintain a constant reduced pressure regardless of inlet pressure fluctuations, making it highly reliable for industrial and commercial water systems.

Features

  • Wetted parts are made of corrosion-resistant material to prevent rusty water.
  • JWWA approval (compliant with the Japanese Water Supply Act). Yoshitake GD-27S-NE JWWA approval mark
  • Reduced noise during operation.
  • Pressure balance structure keeps the reduced pressure at a constant level without being affected by inlet pressure.
  • Closed structure keeps fluid inside even if the diaphragm is damaged or broken.
  • Maintenance and inspection can be conducted easily by disassembling simply from the upper side.
  • Compact and lightweight design makes piping works easy.

Yoshitake GD-27S-NE pressure reducing valve product photo

Specifications

SpecificationValue
ApplicationCold and hot water
Inlet pressure1.0 MPa or less
Reduced pressure(A) 0.05-0.35 MPa, (B) 0.3-0.7 MPa
Minimum differential pressure0.05 MPa
Maximum pressure reduction ratio10:1
Application temperature5-90°C
Body MaterialCast stainless steel
Valve seat MaterialCast stainless steel
Valve disc MaterialFKM
Diaphragm MaterialEPDM
ConnectionJIS 10K FF flanged

INFO

The products of the nominal size 20A to 50A incorporate a strainer (40 mesh). 65A to 100A do not include a strainer. Pressure gauge connection port is JIS R1/4.

Dimensions and Weights

Yoshitake GD-27S-NE dimensions and weight diagram

Nominal sizeL (mm)H (mm)H1 (mm)Weight (kg)
20A160170413.9
25A160170414.8
32A200224578.0
40A200224578.3
50A220239.56110.8
65A2203297720.6
80A2303458222.0
100A2704129434.5

Rated Flow Rate

The differential pressure before and after the valve is 0.15 MPa or more. If the differential pressure is less than 0.15 MPa, refer to the flow rate charts.

Nominal size20A25A32A40A50A65A80A100A
Rated flow rate L/min4060100150250300450700

Flow Rate Chart (15A to 50A)

Yoshitake GD-27S-NE flow rate chart 15A to 50A

Installation and Operation

WARNING

  • When the product is used for hot fluid, do not touch the product with bare hands.
  • Before installing the product in the piping, be sure to remove foreign substances and scale from the piping.
  • Be sure to install a strainer at the inlet side of the product of nominal size 65A to 100A.

Piping Example

Yoshitake GD-27S-NE installation piping example

TIP

Install a safety relief valve for equipment protection at the outlet side of the product. Be sure to install pressure gauges at the inlet and outlet sides of the product for correct pressure adjustment.

Structure and Parts

Yoshitake GD-27S-NE structural exploded view

Key components include the cast stainless steel body, FKM valve disc, EPDM diaphragm, and a pressure balance structure regulated by an alloy steel adjusting spring.