Yoshitake GP-1000HEN Pressure Reducing Valve for Steam

The Yoshitake GP-1000HEN is a pilot-operated pressure reducing valve for steam applications. Featuring an EN PN25 flanged connection, a ductile cast iron body, and a 20:1 max reduction ratio.

Yoshitake GP-1000HEN Pressure Reducing Valve for Steam

Yoshitake GP-1000HEN is a pilot-operated pressure reducing valve designed for steam applications. It features a ductile cast iron body and stainless steel internals, offering precise control over pressure fluctuations and flow rate changes.

Features

  1. The GP-1000HEN is an easy replacement for existing valves because it complies with face-to-face dimensions of the EN standard (except for 15A).
  2. The valve responds very sharply to the fluctuation of inlet pressure and the change of the flow rate, so that the reduced pressure can be kept at a constant level.
  3. Pressure adjustment is easy, and the set pressure range is wide.
  4. Compliant with the standard of SHASE-S106 Pressure Reducing Valves (by the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan).

Specifications

ModelGP-1000HEN / GP-1000H
ApplicationSteam
Inlet pressure0.1-1.6 MPa
Reduced pressure(A) 0.05-0.9 MPa
(B) 0.9-1.4 MPa
90% or less of inlet pressure (gauge pressure)
Minimum differential pressure0.05 MPa
Maximum pressure reduction ratio20:1
Maximum temperature220°C
Valve seat leakage0.01% or less of rated flow rate
Material: BodyDuctile cast iron
Material: Main valve, valve seatStainless steel
Material: Pilot valve, pilot valve seatStainless steel
Material: Piston, cylinderStainless steel
Material: DiaphragmStainless steel
ConnectionEN PN25 flanged

INFO

  • Available with JIS Rc screwed (GP-1010H).
  • For 15A, 20A, ASME flange is not available.

Dimensions and Weights

Nominal sizeL (GP-1000HEN)L (GP-1000H)H (GP-1000HEN)H (GP-1000H)H1Weight (GP-1000HEN)Weight (GP-1000H)
15A150150(-)291285648.08.0(-)
20A150155(-)291285648.58.5(-)
25A160160 (160)3003006710.010.0 (10.0)
32A180190 (180)3333238214.014.0 (14.0)
40A200190 (200)3333238215.514.5 (15.5)
50A230220 (230)3533479321.020.0 (21.0)

INFO

The values in parentheses are the dimensions of ASME Class 300 flanged.

Yoshitake GP-1000HEN dimensions diagram

Yoshitake GP-1000HEN GP-1000H product photo

Specifications Selection Chart

Yoshitake GP-1000HEN specifications selection chart

Find the intersection point of the inlet and reduced pressures. If the intersection point is within range (A) in the chart, the pressures are controllable with a single pressure reducing valve. They can be controlled by two-stage pressure reduction if the intersection point is within range (B). The valve does not fulfill specified performance in range (C).

Characteristic Charts

Pressure Characteristic Chart

Yoshitake GP-1000HEN pressure characteristic chart

This chart shows variation in reduced pressure when the inlet pressure of 1.0 MPa is changed between 0.3 MPa and 1.6 MPa while the reduced pressure is set at 0.1 MPa.

Flow Characteristic Chart

Yoshitake GP-1000HEN flow characteristic chart

  • Shut-off pressure rise: Within 0.02 MPa
  • Offset pressure: Within 0.03 MPa (when the set pressure is between 0.05 MPa and 0.1 MPa); Within 0.05 MPa (when the set pressure is more than 0.1 MPa and 1.4 MPa or less)

Table of Corrected Cv Values

Table of rated Cv values (Cv value when the correction factor C = 1)

Nominal size15A20A25A32A40A50A65A80A100A
Cv values12.346.5916253664

Note

When the reduced pressure is within either of the ranges shown below, calculate the corrected Cv value by multiplying the rated Cv value by the correction factor C obtained from Fig. 1.

  • When the inlet pressure is between 0.7 MPa and 1.0 MPa and the pressure reduction ratio is more than 10:1
  • When the inlet pressure is more than 1.0 MPa and the reduced pressure is 0.4 MPa or less

Fig. 1: Corrected Cv value

Yoshitake GP-1000HEN corrected cv value chart

Nominal Sizes Selection Chart (For Steam)

Yoshitake GP-1000HEN nominal sizes selection chart

When selecting the nominal diameter of a pressure reducing valve with an inlet pressure (P1) of 0.8 MPa, reduced pressure (P2) of 0.05 MPa, and steam flow rate of 600 kg/h, first find the intersection point (C) of the inlet pressure 0.8 MPa and the diagonal line. Then, move left from this point to find the intersection point (D) with the reduced pressure of 0.05 MPa. From point (D), move vertically downward to find the intersection point (E) with the flow rate of 600 kg/h. Since point (E) lies between the nominal diameters 32A and 40A, select the larger diameter, 40A.

TIP

Set the safety factor at 80 to 90%.