Yoshitake GP-1000S pilot-operated pressure reducing valve for steam applications. Features ductile cast iron body, stainless steel trim, 0.1-1.0 MPa inlet pressure, and 20:1 max reduction ratio.

Yoshitake GP-1000S pilot-operated pressure reducing valve is a high-performance solution designed for steam applications. It features a durable ductile cast iron body combined with stainless steel trim components (piston and cylinder) to enhance longevity and reliability. The spherical main valve design ensures exceptional sealability, greatly reducing valve seat leakage to comply with ANSI Class IV standards.


| Specification | Value |
|---|---|
| Application | Steam |
| Inlet pressure | 0.1-1.0 MPa |
| Reduced pressure | 0.05-0.9 MPa (90% or less of inlet pressure) |
| Minimum differential pressure | 0.05 MPa |
| Maximum pressure reduction ratio | 20:1 |
| Maximum temperature | 220°C |
| Valve seat leakage | 0.01% or less of rated flow |
| Connection | JIS 10K FF Flanged |
| Body Material | Ductile cast iron |
| Valve & Valve Seat | Stainless steel |
| Piston & Cylinder (Trim) | Stainless steel (for GP-1000S) |

| Size | L (mm) | H (mm) | H1 (mm) | Weight (kg) |
|---|---|---|---|---|
| 15A | 150 | 285 | 64 | 8.0 |
| 20A | 155 | 285 | 64 | 8.5 |
| 25A | 160 | 300 | 67 | 10.0 |
| 32A | 190 | 323 | 82 | 14.0 |
| 40A | 190 | 323 | 82 | 14.5 |
| 50A | 220 | 347 | 93 | 20.0 |
| 65A | 245 | 357 | 100 | 30.0 |
| 80A | 290 | 404 | 122 | 35.0 |
| 100A | 330 | 450 | 144 | 52.5 |

The pressure-reducing valve lowers pressure by throttling. It comprises the main valve and main valve seat for throttling, and an adjusting spring, diaphragm, pilot valve, and piston for pressure sensing and activation.

Example: For an inlet pressure of 0.6 MPa, reduced pressure of 0.4 MPa, and a steam flow rate of 800 kg/h, find the intersection point of 0.6 MPa and 0.4 MPa. Trace down vertically to the 800 kg/h flow rate. The point lies between nominal sizes 40A and 50A. Select the larger size: 50A.
If the inlet pressure exceeds 0.7 MPa, and the reduced pressure is 0.4 MPa or less, multiply the rated Cv value by the correction coefficient C from the chart below: 
| Nominal size | 15A | 20A | 25A | 32A | 40A | 50A | 65A | 80A | 100A |
|---|---|---|---|---|---|---|---|---|---|
| Rated Cv value | 1 | 2.3 | 4 | 6.5 | 9 | 16 | 25 | 36 | 64 |

Installation Precautions

| Consumable Part | Replace Period |
|---|---|
| Diaphragm | 2 years |
| Piston ring & Inner ring | 3 years |
| Pilot valve assembly | 5 years |
| Gaskets | 2 years |
| Strainer | 5 years |
Pressure Hazard
Before disassembling the valve, be sure that the stop valves at the inlet and outlet sides are closed and all internal pressure and condensate have been safely discharged.
Explore similar products in our catalog